8 Installation actuator/fi eld
module
Mount actuator onto the valve. Wire actuator,
temperature sensor, power supply 24V and C-bus line
inside the fi eld module "FM-CW K" according to the
below wiring diagram.
Disconnect the appliance from the power supply before
starting work. Connection of the appliance to the bus
line and power supply must only be carried out by a
qualified electrician. The field module "FM-CW K"
requires an own power supply with an alternating
Bezeichnung
Beschreibung
voltage of 24 V.
C-Bus
Kommunikationsanzeige für Daten Empfangen und Senden von und an die DDC.
The installation location has to be selected so that the
LEARN
Rückmeldung über erfolgreiches Anmelden am C-Bus MASTER
components are not affected by other heat sources,
such as hot pipework.
The casing must only be mounted into the designated
insulation of the electronic circulation regulating valve,
OV item no.: 1150004, 06 and 1150104, 06, 08. Do not
drill through the rear wall of the casing.
!
CAUTION
The appliance must not be installed in a
Bezeichnung
Beschreibung
hazardous location.
LEARN
Einlernen (Teach in) am C-Bus MASTER
Installation on a flammable base is not
permitted!
Polarity needs not be observed when connecting the
temperature sensor.
10
C-bus
C-bus
C-bus
C-bus
Seite 6 - 8
9
Initial operation
See manual of control unit DDC "CW-BS".
10 Accessories
Connection fi ttings:
Press, solder, weldable and threaded connection
fi ttings
(see accessories)
Oventrop DVD
with calculation programme
for potable water circulation systems
item no.: 9999999
free of charge
11 Maintenance
The valve is maintenance-free.
12 Warranty
Oventrops warranty conditions valid at the time of
supply are applicable.

Publicité