Mounting information
- The drive set is fully configured ex factory.The
drives must be reconfigured using SCS in the
event of changes to the ex-factory configuration
(e.g. when removing a drive from existing set or
integrating a new drive).
- Mount the drives whilst under zero stress. With
that, an even load distribution is provided by all
the drive chains.
- At vertical active pulling application (e.g. for a
skylight) the forces must be rearranged by
software SCS.
- If after mounting, the distance X is greater than 23
mm, null balance with software SCS is neccesary.
Closure Ranges will shift in relation to new zero
point.
Minimum sash height/ -width
x
The details apply to a
non-rotational installation of the drive!
(Window inwards opening)
Standard chain:
Minimum size (mm) = Stroke (mm) x 3.9
Maximum stroke bottom-hung vent: 1000 mm
Maximum stroke side-hung vent: 800 mm
Side bow chain:
Minimum size (mm) = Stroke (mm) x 1,6
Maximum stroke bottom-hung vent: 800 mm
Maximum stroke side-hung vent: 350 mm
8/24
CDC-0252-5-ACB
X
≥ 23 mm ?
x
English
Functional description
ACB bus interface
ACB is used for secure communication between the
drive and compatible D+H control systems. It
enables activation, diagnostics and configuration
with perfect position, directly from the control panel.
In this process, all status messages, such as the
OPEN and CLOSED signals, opening stroke and
drive errors, are transmitted to the control panel.
BSY+ synchronised electronics:
A synchronous group can contain up to 8 drives,
which communicate via bus. Each drive has its own
address, configurable with SCS.
The last drive of a synchronous group is the master,
which controls the other drives, the slaves.
Differences in forces between the drives of a group
are balanced by means of intelligent force and
position control. In the event that a drive
malfunctions, all the drives are automatically cut off.
Troubleshooting
Visual inspection:
Only one master drive is allowed.
The master always has the last address of all the
drives; this can be found on a sticker attached to
the drive. Slaves are numbered downwards from
the master, so that in a group of three drives, for
example, the master is no. 3, with a slave 2 and
slave 1 drive. Please note that this only applies in
the ex-factory configuration. As soon as the drives
are reconfigured with SCS, the ex-factory
addressing no longer applies.
The CDC-0252-5-ACB must be set as master.
Wiring:
Is the drive or drive group wired properly?
See connection plans.
Diagnostics with SCS software:
The SCS software and a BSY+ interface is
required for further troubleshooting or
configuration.
99.827.07 1.2/02/19