KitchenAid KBZU122T Instructions D'installation Et Guide D'utilisation Et D'entretien page 10

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Gas Pressure Regulator
The gas pressure regulator supplied with this side burner must be
used. The inlet (supply) pressure to the regulator should be as
follows for proper operation:
LP Gas:
Set pressure: 11" (27.9 cm) WCP
Inlet (supply) pressure: 11" to 14" (27.9 cm to 35.5 cm) WCP
Natural Gas:
Set pressure: 4" (10.2 cm) WCP
Inlet (supply) pressure: 7" to 14" (17.8 cm to 35.5 cm)
WCP maximum.
Contact local gas supplier if you are not sure about the inlet
(supply) pressure.
Burner Requirements for High Altitude
Input ratings shown on the model/serial rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a
rate of 4% for each 1,000 ft (304.8 m) above sea level. Orifice
conversion is required. See "Assistance or Service" section to
order.
Gas Supply Line Pressure Testing
Testing above ½ psi (3.5 kPa) or 14" (35.5 cm) WCP (gauge):
The side burner and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures greater than
½ psig (3.5 kPa).
Testing below ½ psi (3.5 kPa) or 14" (35.5 cm) WCP (gauge) or
lower:
The side burner must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psig (3.5 kPa).
10
Natural Gas
Side burners are equipped for use with Natural gas. They are
design-certified by CSA International for LP (propane or butane)
gases with appropriate conversion.
Side burners are set for natural gas use and have a pressure
regulator with ¹⁄₂" (1.3 cm) female pipe threads.
A
A. Rear side of burner
B. ¹⁄₂" (1.3 cm) side burner gas pipe
C. New CSA approved outdoor flexible gas supply line
The supply line shall be equipped with an approved shutoff valve.
This valve should be located in the same area as the burner and
should be in a location that allows ease of opening and closing.
Do not block access to the shutoff valve. The valve is for turning
on or shutting off gas to the appliance.
A
A. Gas supply line
B. Open position of shutoff valve
C. To side burner
LP gas conversion from a local LP gas supply:
Conversion must be made by a qualified person. A qualified
natural gas technician shall provide the LP gas supply to the
selected side burner location in accordance with the National
Fuel Gas Code ANSI Z2223.1/NFPA54 latest edition, and local
codes.
To convert to LP gas, the LP Gas Conversion Kit Number
W10118099 must be used. Follow Instructions included with kit.
LP gas conversion using a 20 lb LP fuel tank:
To convert to LP gas, the LP Gas Conversion Kit Number
W10118099 must be used. Follow Instructions included with kit.
A 20 lb (9.1 kg) LP gas fuel tank must be purchased separately.
B
C
B
C

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Kbzu242t

Table des Matières