3
4
6
Disassemble the AC connector. Deal with the seals with the diameter of Grid and EPS cable used.
Thread the stripped Grid and EPS cable through
7
the AC connector.
Insert AC terminals into the L1, L2, L3, N and PE conductor
of Grid and EPS cable. Crimp terminals with a hydraulic
9
plier.
1
Connect the assembled EPS cable to the EPS terminal
11
block on the inverter. Tighten terminals with M6 screws.
62
1
2
Hydraulic
plier
2
M6
5±1 N·m
Seal No. Diameter of the seal
bore (mm)
1
34
2
39
3
44
4
49
* Installers remove seals from a smaller to a larger one in
accordance with the diameter of cables selected. If the
diameter of the cable used is over 33 mm, remove the
smallest seal No.1. If the diameter of the cable is 29~33
mm, cut the membrane inside the seal No.1 and thread
cable through it.
Thread heat shrink tubings through the L1, L2, L3, N and
8
PE cable of Grid and EPS cable respectively.
Use a heat gun to attach the tubing to the junction
10
between the terminal and the stripped cable.
1
4
Connect the assembled Grid cable to the Grid terminal
12
block on the inverter. Tighten terminals with M6 screws.
Diameter of cable
selected (mm)
29~33
33~38
38~43
43~48
Heat gun
2
3
M6
5±1 N·m