Press up arrow twice to -21.0ºC. Press SC once to save
setting.
Table 7. Parameter List
Category
Abv
tHE
SEt
SPr
diF
HSE
LSE
dEF
dFt
Add
dtt
drt
dii
dAi
dit
dAt
dot
fdd
ftd
dFa
dCt
doC
dEt
ddt
idi
idd
CoP
uPt
uLi
uLo
uHi
16 |
Operation
Description
Thermostat settings
Set Point
Set Point Adjustment Ratio
Differential
High Set Point
Low Set point
Defrost Settings
Def. Type
Adaptive Defrost
Def Terminate Temp
Def Reset Temp
Def Min Interval
Def Max Interval
Def Min Time
Def Max Time
Drip Off Time
Fan Delay After Defrost
Fan Start Temp
Defrost Fan On
Defrost On Compressor Time
Defrost by Comp. Running Time
Defrost Start Evaporator Temp
Defrost Delta T
Initial Defrost Interval
Initial Defrost Duration
Compressor Settings
Voltage Protection
Minimum Cut-in Voltage
Minimum Cut-out Voltage
Maximum Voltage
-
Then press snowflake button twice.Display will return to
cabinet temp.
Settings
-23
1
2.0
-19.0
-27.0
EL
Yes
5.0 for 45 cu ft
1.6 for 25 cu ft
4.3
1
6
5
60
1
20
-23.2
No
Yes
2
-43
2.1
4
999
No
0
0
270
General Purpose Freezers