5.7. Suspensions
An external suspension set including Silent blocks (Grommets) and spacers (sleeves) come as standard with all Tecumseh compressors. The role of
these silent blocks is to reduce the transmission of vibrations generated by the compressor to the base on which it is mounted. In order to ensure
this function properly, silent blocks should not be constrained. For this, the washer pressing on the spacer must leave a clearance of 1 to 4 mm from
the top of the silent block. In order to not distort the spacer, apply a tightening torque of between 8 to 13 Nm for the M8 screws.
5.8. Electrical connections
Electrical connections will be made before the refrigeration system is charged with refrigerant.
To preserve the quality of the Tecumseh compressor and the safety of the installation and ensure their proper operation, it is imperative to:
• Always wire the compressor when it is switched off.
• Validate the compatibility of the installation's power voltage with that of the compressor (see the nameplate).
• Validate the compatibility of the compressor's electrical drawing with that of the installation.
• Size the connecting cables (power, control) according to the characteristics of the installed compressor (see nameplate).
• Protect the power line and install a grounding line.
• Make electrical connections in accordance with the country's current regulations.
• Use the electrical components that come with the compressor, even if others seem acceptable.
The electric box must always be fixed vertically.
Dimensions
L
H
P
X
Y
A
B
Assembly drawing for Protective cover for FH