Communication with the user via LED backlight:
LED ring light colour
Continuous green
Short green flashing
Flashing of two colours: green and red Abnormal situation
Flashing in red
LED is not lit
Detailed instructions for the Wilo Yonos Para pump itself – to be downloaded at
What it means
Diagnosis
Regular operation
Regular operation of the
pump
Air venting in process
For 10 minutes the pump is
operating in special
conditions to proceed to the
most effective removal of air
bubbles from the system
Once the procedure
completed, enter the setting
according to which the pump
is to operate
The pump will start again
(the pump is
when the abnormal situation
running, but from
comes to an end
time to time it stops)
Stop of pumps (e.g.
Reset the pump
due to a blockage)
Recheck the LED
No power
No power supply for
electronics
7
Cause
What to do
Pump in running
order
1. Too low or too
1. Check the
high voltage: U<160V
voltage:
or U> 253V
195V<U<253V
2. Module
2. Check the
overheated: Engine
medium temp. and
temp. too high
the ambient temp
The pump can not
Replace the pump
start itself because of
a permanent error.
1. The pump is not
1. Check the
connected to power
connection
2. LED is damaged
2. Check if the
pump is running
3. Electronics is
3. If not, replace
damaged
the pump
www.capricorn.pl