Application:
Pumping and mixing set is used in surface heating systems of mixed assembly. Essential functions of the set:
Reduces temperature of high-temperature circuit fluid for the purpose of a low-temperature surface heating system
Assurance of continuous heat transfer fluid flow in separate surface heating loops
Protection of the surface heating installation against overheating
Structure:
1.
Thermoregulating valve (1)
2.
Thermostat head (2) with remote clip-on temperature sensor and
fixing elements. Setpoint temperature range: 20÷65
3.
Temperature sensor (3)
4.
Return control valve (4)
5.
Clip-on electric controller (5) with fixing elements. Setpoint
temperature range: 20÷90°C, 230V, 15A
6.
Circulating pump (6)
Parameters of sets:
type of set
9-3680-045-00-22-13NEW
9-3680-045-00-36-12NEW
2
up to 45 m
9-3681-045-00-22-13
9-3681-045-00-36-12
9-3680-085-00-22-13NEW
9-3680-085-00-36-12NEW
2
up to 85 m
9-3681-085-00-22-13
9-3681-085-00-36-12
9-3680-120-00-22-13NEW
9-3680-120-00-36-12NEW
up to 120
2
m
9-3681-120-00-22-13
9-3681-120-00-36-12
9-3680-160-00-22-13NEW
9-3680-160-00-36-12NEW
up to 160
2
m
9-3681-160-00-22-13
9-3681-160-00-36-12
Pump parameters:
Circulating pumps of sets for
up to 45m
Type
Wilo Star RS 15/4
Lifting height
4m
Temperature range
-10÷+110°C
Network connection
1~230 V, 50 Hz
Protection level
IP 44
Maximum working
10 bar
pressure
Rated power
0.017 kW
Maximum rotational
2350..2720 rpm
speed
Assembling and running
Connecting the set to delivery system and floor heating
manifold:
The assembly delivery system is to be connected to the
thermoregulating valve (1) armed with a thermostat head (2) with
a clip-on sensor (3). The clip-on sensor examines the floor heating
system return temperature and controls the thermostat head, by
opening or closing the regulating valve letting hot water flow into
the system. The system is protected against overheating by an
electric pump controller with a sensor (5), turning the pump off at
the moment of exceeding a set temperature value. The regulating
valve (4) can throttle the return flow to the delivery system. The
assembly is additionally equipped with a by-pass with possibility of
throttling due to a regulating valve installed (6).
components installed must be sealed and leak proof tested
Installation and electrical connection:
Caution!
DANGER! Improper installation and electrical connection
may result in a fatal electric shock. Electrical connections are to be made by a licensed electrician with qualifications recognized
by the local electricity supplier and in accordance with applicable regulations. Type of current and voltage must be as the ones
given on the rating plate. Accident prevention regulations must be observed.
EN – Pumping And Mixing Set Product Manual
code
Wilo Star RS 15/4
Wilo Star RS 15/4
Wilo Yonos Para RS 15/6 RKA
Wilo Yonos Para RS 15/6 RKA
Wilo Star RS 15/4
Wilo Star RS 15/4
Wilo Yonos Para RS 15/6 RKA
Wilo Yonos Para RS 15/6 RKA
Wilo Star RS 15/6
Wilo Star RS 15/6
Wilo Yonos Para RS 15/6 RKA
Wilo Yonos Para RS 15/6 RKA
Wilo Star RS 15/6
Wilo Star RS 15/6
Wilo Yonos Para RS 15/6 RKA
Wilo Yonos Para RS 15/6 RKA
2
2
and up to 85m
Caution!
o
C
thermoregulating
pump type
valve diameter
Circulating pumps of sets for
2
up to 120m
and up to 160m
Wilo Star RS 15/6
6m
-10÷+110°C
1~230 V, 50 Hz
IP 44
10 bar
0.039 kW
2480..2840 rpm
all
5
return valve
diameter
3/8"
1/2"
1/2"
3/4"
3/4"
1"
1"
1"
Energy-saving electronic
2
circulating pump
Wilo Yonos Para RS15/6 RKA
6.2m
0÷+95°C
~230 V +10%/-15%, 50/60 Hz
(ICE 38 standard)
IPx4D
6 bar
0.003-0.036 kW
4350 rpm
thermoregulating
valve KVS
1.7
1.85
1.95
2.2