DIP SW
Description
OFF:* Front cover tamper activated
3
Back Tamper Bypass:
ON: Back tamper bypassed
OFF:* Back tamper activated
4
Charge Current:
ON:* 400 mA Charge current
OFF: 200 mA Charge current
5
Override Battery Discharge Protection:
ON: The battery may be totally discharged during continuous AC failure,
thus battery replacement may be required (no deep discharge protection).
Note: In this position, the repeater will start to operate from a battery whether it
is connected to the mains or not.
OFF:*/** If an AC power occurs, the repeater automatically disconnects
the battery when its backup battery voltage drops below 3.2 VDC in order
to prevent deep discharge that may damage the battery.
Note: In this position, the repeater will not start to operate from a battery power
supply unless first connected to the mains.
6
Spare
7
Spare
8
Programmer Mode:
ON: Programmer Mode (for factory use)
OFF:* Normal Operation
* Default
** Dip Switch 5 should always be set to OFF to ensure battery protection
4