DUAL COMPRESSOR PACKAGED HEAT PUMP INSTALLATION GUIDE
General Installation Information cont.
Figure 3: Hanger Location and Assembly
ISO VIEW
Corner #3
Corner post #1 is the post with the water line connections. From a top view,
proceed clockwise around the unit for posts 2, 3, and 4.
Weight Distribution
Vertical
Model
Weight
lb
198
024
kg
90
lb
221
036
kg
100
lb
303
048
kg
137
lb
329
060
kg
149
lb
350
072
kg
159
Corner #4
Corner #2
Horizontal Weight Distribution
Horizontal
Front
Weight
1
2
228
69
63
103
31
29
250
80
65
113
36
29
325
93
97
147
42
44
358
110
100
162
50
45
369
141
78
167
64
35
Corner #1
Hanger Bracket Locations
Model
Back
3
4
024
73
23
33
10
70
35
036
32
16
101
34
048-060
46
15
103
45
070
47
20
71
79
32
36
8/3/2014
10
(See Figure 3)
Hanger Kit
Unit Hanger Dimensions
Part Number
A
in.
53.7
99S500A04
cm.
136.4
in.
63.7
99S500A04
cm.
161.8
in.
72.7
99S500A03
cm.
184.7
in.
77.7
99S500A03
cm.
197.4
B
C
D
25.1
21.4
n/a
63.8
54.4
n/a
25.1
21.4
n/a
63.8
54.4
n/a
28.1
24.4
29.3
71.4
62.0
74.4
28.1
24.4
29.3
71.4
62.0
74.4