Daikin RXA42B5V1B8 Manuel D'installation page 9

Masquer les pouces Voir aussi pour RXA42B5V1B8:

Publicité

Troubleshooting (see "12 Troubleshooting" [ 4  17])
DANGER: RISK OF ELECTROCUTION
▪ When the unit is NOT operating, the LEDs on the PCB
are turned OFF in order to save power.
▪ Even when the LEDs are OFF, the terminal block and
the PCB may be powered.
3
About the box
3.1
Outdoor unit
3.1.1
To remove the accessories from the
outdoor unit
a
b
c
a
General safety precautions
b
Outdoor unit installation manual
c
Fluorinated greenhouse gases label
d
Multilingual fluorinated greenhouse gases label
e
Drain plug (located on the bottom of the packing case)
f
Drain cap (1)
g
Drain cap (2)
h
Energy label
4
Unit installation
WARNING
Installation shall be done by an installer, the choice of
materials and installation shall comply with the applicable
legislation. In Europe, EN378 is the applicable standard.
4.1
Preparing the installation site
WARNING
The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating ignition sources (e.g. open flames, an operating
gas appliance, or an operating electric heater). The room
size shall be as specified in the General safety precaution.
4.1.1
Installation site requirements of the
outdoor unit
Mind the following spacing guidelines:
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9),
RZAG-B
R32 split series
3P766062-2 – 2024.01
d
e
f
g
>100
>350
b
a
b
a
>50
b
h
a
>50
a
Air outlet
b
Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.
Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom), so that the operation noise will cause no trouble.
Note: If the sound is measured under actual installation conditions,
the measured value might be higher than the sound pressure level
mentioned in "Sound spectrum" in the data book due to
environmental noise and sound reflections.
INFORMATION
The sound pressure level is less than 70 dBA.
The outdoor unit is designed for outdoor installation only and for
ambient temperatures specified in the table below (unless otherwise
specified in the operation manual of the connected indoor unit).
Model
ARXM50, RXM50+60
RXA, ARXF,
ARXM60+71, RXM71
RXF, RXP
RZAG-B
4.1.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
3 About the box
>350
b
>100
a
a
>100
Cooling
Heating
–10~50°C DB
–20~24°C DB
–10~46°C DB
–15~24°C DB
–10~48°C DB
–15~24°C DB
–20~52°C DB
–20~24°C DB
Installation manual
a
>50
b
>100
>350
b
(mm)
9