4 Unit installation
c
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
It is recommended to provide at least 150  mm of free space below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
level of snow. If necessary, construct a pedestal. See
unit" [ 4  10] for more details.
the outdoor
In heavy snowfall areas it is very important to select an installation
site where the snow will NOT affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.
4.2
Mounting the outdoor unit
4.2.1
To provide the installation structure
Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.
Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field
supply).
Installation manual
10
a
c
b
"4.2 Mounting
(mm)
a
100 mm above expected level of snow
4.2.2
To install the outdoor unit
4.2.3
To provide drainage
NOTICE
If the unit is installed in a cold climate, take adequate
measures so that the evacuated condensate CANNOT
freeze.
NOTICE
If the drain holes of the outdoor unit are blocked up by a
mounting base or floor surface, place additional foot bases
≤30 mm under the outdoor unit's feet.
INFORMATION
For information on the available options, contact your
dealer.
1 Use a drain plug for drainage.
2 Use a Ø16 mm hose (field supply).
a
Drain port
b
Bottom frame
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9),
4× M8/M10
b
a
c
d
RZAG-B
R32 split series
3P766062-2 – 2024.01