To close the drain holes and attach the drain
socket
NOTICE
In cold areas, do NOT use a drain socket, hose and caps
(1, 2) with the outdoor unit. Take adequate measures so
that the evacuated condensate CANNOT freeze.
1 Install drain caps 1 and 2 (accessory). Make sure the edges of
the drain caps close off the holes completely.
a
b
a
Bottom frame
b
Drain cap
2 Install the drain socket.
a
b
c
b
b
a
a
a
Drain hole. Install a drain cap (2).
b
Drain hole. Install a drain cap (1).
c
Drain hole for drain socket
5
Piping installation
5.1
Preparing refrigerant piping
5.1.1
Refrigerant piping requirements
CAUTION
Piping and joints of a split system shall be made with
permanent joints when inside an occupied space except
joints directly connecting the piping to the indoor units.
NOTICE
The piping and other pressure-containing parts shall be
suitable for refrigerant. Use phosphoric acid deoxidised
seamless copper for refrigerant piping.
▪ Foreign materials inside pipes (including oils for fabrication) must
be ≤30 mg/10 m.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
Model
Liquid pipe
RZAG35, RXA42
RZAG50+60, RXA50,
ARXM50+60,
RXM50+60, RXP,
RXF, ARXF
RXM71
ARXM71
Refrigerant piping material
▪ Piping material: phosphoric acid deoxidised seamless copper
▪ Flare connections: Only use annealed material.
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9),
RZAG-B
R32 split series
3P766062-2 – 2024.01
Pipe outer diameter (mm)
Gas pipe
Ø6.4
Ø9.5
Ø6.4
Ø12.7
Ø6.4
Ø15.9
Ø9.5
Ø15.9
▪ Piping temper grade and thickness:
Outer diameter
Temper grade
(Ø)
6.4 mm (1/4")
Annealed (O)
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
(a)
Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.
5.1.2
Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035
and 0.045 kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness:
Pipe outer diameter
Insulation inner
)
diameter (Ø
p
6.4 mm (1/4")
8~10 mm
9.5 mm (3/8")
10~14 mm
12.7 mm (1/2")
14~16 mm
15.9 mm (5/8")
16~20 mm
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20  mm to prevent condensation on the surface of the
insulation.
5.1.3
Refrigerant piping length and height
difference
What?
Maximum allowable pipe length
Minimum allowable pipe length
Maximum allowable height
difference
5.2
Connecting the refrigerant piping
DANGER: RISK OF BURNING/SCALDING
CAUTION
▪ No brazing or welding on site for units with R32
refrigerant charge during shipment.
▪ During installation of the refrigeration system, joining of
parts with at least one part charged shall be performed
taking into account the following requirements: inside
occupied spaces non-permanent joints are NOT
allowed for R32 refrigerant except for site made joints
directly connecting the indoor unit to piping. Site made
joints directly connecting piping to indoor units shall be
of non-permanent type.
5 Piping installation
(a)
Thickness (t)
Ø
≥0.8 mm
t
≥1 mm
Insulation thickness
)
(t)
i
≥10 mm
≥13 mm
≥13 mm
≥13 mm
Distance
ARXF, RXF,
RZAG-B
RXP, ARXM,
RXM, RXA
30 m
50 m
3 m
3 m
20 m
30 m
Installation manual