Télécharger Imprimer la page

Watts Febco LF866-FS Serie Manuel D'installation, D'entretien Et De Réparation page 3

Masquer les pouces Voir aussi pour Febco LF866-FS Serie:

Publicité

Les langues disponibles

Les langues disponibles

Service and Maintenance
• Rinse all parts with clean water before reassembly.
• Do not use any pipe dope, oil, grease, or solvent on any parts
unless instructed to do so.
• Do not force parts. Parts should fit together freely. Excess force
can cause damage and render the assembly inoperable.
• Carefully inspect seals and seating surfaces for debris or damage.
• After servicing, repressurize the assembly and test to ensure
proper operation.
• For more information on maintenance, check with your FEBCO
representative or go to FEBCOonline.com.
Check Valve Disassembly
1. Close the outlet shutoff valve, then close the inlet shutoff valve.
Bleed residual pressure from the assembly by opening test
cocks No. 4, No. 3, and No. 2 in this sequence.
2. Remove the cover nuts and bolts and lift the cover from
the body. The springs are retained and the cover should be
pushed away from the body approximately 1/4 inch.
3. Inspect the parts and debris from the disc and seat ring.
Replace worn or damaged parts as required.
4. Replace the cover, making sure the spring assembly is
positioned in the pivot socket. If necessary, apply FDA
Approved grease to the O-ring groove in the body to keep
the O-ring in position while installing the cover.
5. Install the bolts and nuts and tighten.
Troubleshooting
PROBLEM
Continuous relief valve discharge
Intermittent relief valve discharge
Low flows passing through mainline valve (RPDA)
Add-on and Retrofit Sensor Connection Kits for Building Management Systems
PART NUMBER
88009414
88009415
Add-on and Retrofit Sensor Connection Kits for Cellular Communication
PART NUMBER
88009416
88009417
Debris on check seating surfaces
Debris on relief valve surfaces
Inlet pressure fluctuations
Downstream pressure surges
Mainline check fouled
ADD-ON/RETROFIT KIT
FP-FBF-BMS-21/2-10
BMS Sensor Connection Kit
Series LF860-FS Large, LF866-FS, LF880V-FS, LF886V-FS
Sizes 2½" to 10"
FP-RFK-FBF-BMS-CFS-21/2-10
BMS Sensor Retrofit Connection Kit
Series LF860 Large, LF866, LF880V, LF886V
Sizes 2½" to 10"
ADD-ON/RETROFIT KIT
FP-FBF-CFS-21/2-10
Cellular Sensor Connection Kit
Series LF860-FS Large, LF866-FS, LF880V-FS, LF886V-FS
Sizes 2½" to 10"
FP-RFK-FBF-CFS-21/2-10
Cellular Sensor Retrofit Connection Kit
Series LF860 Large, LF866, LF880V, LF886V
Sizes 2½" to 10"
Relief Valve Disassembly
1. Detach the activation module, if installed, from the flood sensor.
2. Use two ½" wrenches to remove the sensor from the relief valve.
3. Remove the cap screws holding the cover to the relief valve
body, and remove the cover.
4. Remove the diaphragm and pull the internal assembly from
the body. If helpful, push the internal assembly with fingers
through the discharge opening.
5. Inspect for debris, damage, or fouling of the seat disc. Clean
or replace parts as required.
6. Reassemble in the reverse order of disassembly.
Test Procedure for Reduced Pressure Assemblies
Check the ASSE Series 5000 manual for an appropriate test
method that is consistent with local codes of the area.
CAUSE
Disassemble and clean
Eliminate fluctuations
Eliminate surges
Disassemble and clean
Includes sensor activation module with cable, ground wire, and power
adapter. Use this kit to activate the integrated flood sensor and enable flood
detection capabilities on the relief valve of a new installation linked to a BMS
controller (not included).
Includes flood sensor with mounting hardware, sensor activation module
with cable, ground wire, and power adapter. Use this kit to install the flood
sensor and enable flood detection capabilities on the relief valve of an exist-
ing installation linked to a BMS controller (not included).
Includes sensor activation module with cable, Cellular Gateway with mount-
ing kit, ground wire, and power adapter. Use this kit to activate the integrat-
ed flood sensor and enable flood detection capabilities on the relief valve of a
new installation linked to a cellular network to send alerts by email message,
SMS text message, or voice call.
Includes flood sensor with mounting hardware, sensor activation module
with cable, Cellular Gateway with mounting kit, ground wire, and power
adapter. Use this kit to install the flood sensor and enable flood detection
capabilities on the relief valve of an existing installation linked to a cellular
network to send alerts by email message, SMS text message, or voice call.
SOLUTION
DESCRIPTION
DESCRIPTION
3

Publicité

loading

Ce manuel est également adapté pour:

Febco lf860-fs serie