BEFORE INSTALLATION
The LP916A, B and C Pneumatic Remote Bulb Thermostats
provide proportional control of heating or cooling in induction
units, fan coil units and unit ventilators. A wide throttling range
model is available for duct discharge control of heating or
cooling coils and mixed air dampers.
CAUTION
Equipment Damage Hazard.
Do not rotate the thermostat control shaft more than
two revolutions clockwise from the original position as
received. Rotating the shaft more than two revolutions
from the original position can cause permanent
damage to the thermostat.
The caution is also on a removable tag attached to the
thermostat and should remain attached until the system is
ready to start up. See Fig. 1.
® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved
LP916A, B and C Pneumatic
Remote Bulb Thermostats
Fig. 1. The LP916 caution label removable tag.
Use care to prevent the capillary and sensing bulb from being
dented or damaged during installation. Avoid any sharp bends
or kinks in the capillary.
INSTALLATION INSTRUCTIONS
CAUTION
DO NOT
ROTATE SETPOINT SHAFT
MORE THAN TWO COMPLETE
CLOCKWISE REVOLUTIONS
FROM ITS 'AS RECEIVED'
CONDITION - THE DEVICE
MAY BE PERMANENTLY
DAMAGED
C4646
95-5559EF

Publicité

loading

Sommaire des Matières pour Honeywell LP916B

  • Page 1 Fig. 1. The LP916 caution label removable tag. Use care to prevent the capillary and sensing bulb from being dented or damaged during installation. Avoid any sharp bends or kinks in the capillary. ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved 95-5559EF...
  • Page 2 INSTALLATION Integral Mounting Bracket Model 2. Mount the thermostat in the location where the mount- ing screws are readily accessible and the setpoint knob The LP916 integral mounting bracket model includes two easily reached. Preferably the scale is visible from the Tinnerman nuts, two sensing bulb hangers and two No.
  • Page 3 NOTE: When air connections are towards the back, connect the appropriate lengths of tubing to the barb connec- tors before mounting. Duct Mounting Duct mounting requires a 107324A duct bulb holder. See Fig. 7. The sensing bulb should be located in the duct where air of representative temperature can freely circulate.
  • Page 4 CAPILLARY 4-7/8 (124) 4-1/2 (115) BE SURE THIS TUBE IS UNDER 2-3/16 (56) 2-1/16 (53) BULB HOLDER, AS SHOWN M18343 C4653 Fig. 9. Mounting the capillary tubing in the bulb holder. 6. Insert the bulb and bulb holder into the duct through the Fig.
  • Page 5 CAPILLARY MAIN BRANCH 3-1/4 PROTECTED BARBS (83) THERMOSTAT CONTROL SHAFT SCALEPLATE 10-32 x 1/4-IN. SCREW (2) (16) 1-7/8 (48) 2-3/4 (70) C4648 SETPOINT KNOB Fig. 15. Mounting bracket in 316016A bag assembly. Dimensions are in in. (mm). SENSING BULB C4652 Fig.
  • Page 6 4. Hold the thermostat in place and mark the screw hole NOTE: Tinnerman nuts can be used by making clearance centers in the terminal unit. See Fig. 17. holes for the screws. 5. Punch or drill pilot holes in the mounting surface for sheet metal screws.
  • Page 7 RETURN AIR Table 1. Throttling Ranges and Scale Increment Values. M5416 Setpoint Throttling Range in F Range in Fig. 20. Typical LP916B fan coil application, heating and Scale Increments Degrees F (K) cooling with seasonal changeover. WARMER-COOLER/0.9F 3.5 (2) 65-85 (18-29)
  • Page 8 IMPORTANT When making adjustments, always allow enough SWITCHOVER time (up to three minutes) for the branch pressure to SPRING M7997 STUD ADJUSTING NUT stabilize. Fig. 22. The LP916B automatic switchover mechanism. �������������������������������� ��������� ����������������������������������� ������������������������ ���������������� ������������������������ �������������������� ������� Printed in U.S.A. on recycled 95-5559EF J.H.
  • Page 9 Prendre garde d'endommager ou de plier le tube capillaire ou le bulbe au moment de l'installation. S'assurer que le tube capillaire n'est pas plié à angle aigu. ® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved 95-5559EF...
  • Page 10 THERMOSTATS PNEUMATIQUES Ω BULBE Ω DISTANCE LP916A, B ET C INSTALLATION 4. Monter le bulbe dans l'un ou l'autre des compartimants E. Voir la Fig. 3. Prendre garde de plier à angle aigu, de tortiller ou de pincer le tube capillaire de 914 mm (36 po).
  • Page 11 THERMOSTATS PNEUMATIQUES Ω BULBE Ω DISTANCE LP916A, B ET C 4. Passer le bulbe et le tube capillaire dans l'ouverture de l«ouverture défonçable. Placer le bulbe entre le filtre de reprise d'air et le serpentin. Poser une garniture d'étanchéité dans la paroi de l'unité pour protéger le tube capillaire.
  • Page 12 THERMOSTATS PNEUMATIQUES Ω BULBE Ω DISTANCE LP916A, B ET C Modèle avec trousse de montage Le modèle avec trousse de montage LP916 est illustré à la TUBE CAPILLAIRE Fig. 12. Ce modèle peut être monté sur un panneau ou dans une unité...
  • Page 13 THERMOSTATS PNEUMATIQUES Ω BULBE Ω DISTANCE LP916A, B ET C TUBE CAPILLAIRE CANALISATION PRINCIPALE CANALISATION SECONDAIRE CANNELURES PROTÉGÉES (3-1/4) THERMOSTAT ARBRE DE COMMANDE PLAQUE GRADUÉE (5/8) 48 (1-7/8) 70 (2-3/4) CF4648 VIS 10-32 x 1/4 PO(2) Fig. 15. Support de montage de l'ensemble 316016A. BOUTON DE RÉGLAGE Encombrement en mm (po).
  • Page 14 THERMOSTATS PNEUMATIQUES Ω BULBE Ω DISTANCE LP916A, B ET C 4. Tenir le thermostat à l'endroit où il sera posé et marquer REMARQUE : Pour une installation avec des rivets à tôle, le centre des trous de vis dans l'unité terminale. Voir la faire des trous de passage pour les vis.
  • Page 15 MF5416 REMARQUE : Attendre que la pression s'établisse dans la canalisation secondaire (jusqu'à trois minutes). Fig. 20. Application type du LP916B dans un ventilo-convecteur - chauffage ou Se reporter au Tableau 1 pour les valeurs incrémentielles de refroidissement selon la saison.
  • Page 16 (jusqu'à trois minutes). By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...

Ce manuel est également adapté pour:

Lp916aLp916cLp916a1159/u