Top View
Side View
SNH210(H4)
-- The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national
requirements.
-- Turn power off before inspection, installation or removal.
-- Before using, external earthing is must required. Earthing is also must required in its whole life.
-- The Luminaire must be used within the applicable product specifications, installation instructions and environmental conditions for storage &
operations according to application guidelines provided by Signify for product Warranty to be valid.
-- The corrosive atmosphere or hazardous materials such as sulfur, chlorine, phthalate, etc must be avoided during the use and storage.
-- The manufacturer will not take responsibility caused by improper use or self-modifications of the product.
-- If the external flexible cable or cord of this luminaire is damaged. It shall be exclusively replaced by the manufacturer or his service agent or a
similar qualified person in order to avoid a hazard.
-- For Indoor use only. This product is not suitable for cold storage areas where obvious temperature gradients are present, such as ventilation
opening, door, etc.
--
Installer needs to arrange Chain / Pipe for mounting. The default product is supplied with a mounting hook
-- The height between luminous surface and ground suggested be more than 5m; the height between bottom of luminaire and mounting surface
must be more than 0.3m.
-- Similar installation or application like flood and tunnel luminaires are NOT allowed.
-- Not suitable for use in harsh vibration and often causing vibration or swinging environment. Also, not suitable for area prone to hurricane
and extreme winds.
-- If customer require the luminous surface levelness<1°,the pipe mounting method is recommended, and suggest to use gradienter to precisely
measure and adjust.
-- Periodic cleaning of the luminaire optical lens cover will ensure maximum optical efficiency.Luminaire shall be cleaned with a dry soft cloth
only.
-- The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
-- The control gear contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
-- This product contains a light source of energy efficiency class: C.
This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible
harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of
material resources. To return your used device, please use the return and collection systems or contact the retailer where the product
was purchased. They can take this product for environmental safe recycling.
Sensor far away from heat source
Sensor far away from air outlet
Position (m)
> 2m
3/6
Disclaimer:
1. In these plots, the white areas are blind spots and the
detection is based on subject's motion. An idle subject
may not continue to trigger occupancy detection once
the hold time expires.
2. As PIR based sensing works on temperature difference
between the subject and the ground level, the
occupancy detection could vary due to clothing and size
of subject.
Warning:
Place heat radiating devices outside of the monitoring cone.
Avoid drafts (e.g. from ventilators or heating systems).
Light sensor:
The light sensor measures the total amount of light with an
opening angle of 10° whereas PIR has 30°, all calculated from
normal. The following aspects should be observed during
installation: Minimum distance from the window ‐ refer below
graph
Prevent light reflections from outside entering the sensor (for
example sunlight reflection from a car/truck bonnet) as this will
lead to incorrect light regulation.
As a guideline the formula 0.174 x H can be used to calculate the
minimum distance between the window and sensor whereby H
is the height from the top of the window to the ceiling.