Basket Fan 130
30°
Illustration 2: Allowed tilt angle range
Condensate drain holes
The fan motor has drain holes to allow condensation that may form inside the
motor to leave the motor. After installation, the drain hole at the lowest point
of the motor must be open, the other drain holes must be closed.
Spare condensate drain plugs are supplied with the fan. Keep all the drain
plugs as they must be temporarily reinserted in the open drain holes during
wet cleaning.
Illustration 3: Condensate drain plug
Guarding
NOTICE
The fan must be guarded according to local regulations
The guards of this fan have coarse spaced openings. These guards do not
provide the required safety distances to prevent hazard zones being reached
by upper and lower limbs (ISO 13857).
WARNING
The fan must be installed with the lowest moving part at least
2,7m above floor or reference level.
5.2

Electrical

Wiring diagrams
NOTICE
Electrical connection must be carried out by a qualified electri-
cian. Electrical connections must be made in accordance with
local regulations.
Check the rating plate and verify that this fan is suitable for the available
power supply.
For 3~ fan motors: check that STAR / DELTA is properly configured on the
terminal block.
INS00018-C
Original instructions
1~
TB
L
Illustration 4: 1~
3~
L1
L2
L3
Illustration 5: 3~ STAR / DELTA (standard terminal block)
3~
L1
L2
3~
L1
L2
Illustration 6: 3~STAR / DELTA with optional thermal detectors (thermostats)
Control
This fan is supplied without a control or control system. A control or a control
system must be provided for operation of the fan.
Isolator
This fan is supplied without an electrical isolator. An electrical isolator must be
provided to facilitate safe maintenance and troubleshooting.
Grounding
The fan must be grounded. Ground the fan according to local
regulations.
N
3~
L1
L2
L3
L3
TB
TB
L3
TB
TB
ENGLISH | 7