1. general inFOrMatiOn
a. Your heater comes fully assembled and is tested at
the factory for proper gas and input as stated on
the name plate.
b. Before proceeding with the installation, be sure to in-
spect for damages. The freight company that delivered
the heater must be notified of any damages prior to
installation. HeAT sTAR will send replacement parts for
damaged parts only after receiving a signed inspection
report to prove the liability of the freight company.
c. Do not attempt to operate heater with any other gas
than that indicated on the heater name plate.
d. Installation of the heater must conform with local
building codes or, in absence of local codes, with
the National Fuel Gas Code, ANsI Z223.1/NFPA54. In
Canada, refer to CAN 1-B146.1.
e. Plugged 1/8" N.P.T. Test Gage Connection is located
on the Heater Gas Control or a N.P.T. Connection is
located on the outside of the Cast Venturi.
2. clearances Minimum clearances to combustibles.
(refer to Figure 1)
Provide adequate clearance to combustibles, Figure 1,
between control end of heater for servicing and mini-
mum on top and sides for ventilation and combustion
air supply.
A minimum clearance of 8' above floor for public
garages in accordance with ANsI/NFPA No. 88 most re-
cent edition or Figure 1; whichever is larger. In Canada
refer to CAN 1-B149.1 Installation codes for Gas burn-
ing appliances.
A minimum clearance of 10' from the bottom of heater
to top of wing, or engine enclosure, where aircraft are
housed, and 8' above floor in other areas of the hang-
er in accordance with ANsI/NFPA No. 409 most recent
edition, or Figure 1; the larger dimension of ANsI/NFPA
No. 409 or Figure 1 is to be used. In Canada refer to
CCA B149-1-M91.
warning:
MAINTAIN CleARANCes As sHoWN
IN FIGURe 1 oR oN HeATeR NAMePlATe, IN GARAGe
INsTAllATIoNs WHeRe PARKeD VeHICles ARe DI-
ReCTlY BeloW THe HeATeR.
3. suspensiOn
Heater has four mounting holes, two on each end, for
attaching rod or angle iron brackets and shall be safely
and adequately fixed in position independent of gas
and electric supply lines. Refer to Figures 4, 5, and 7 on
pages 13 and 14 for recommended suspensions.
4. gas supplY
Provide adequate gas supply for rated input of each
heater using American standard Installation of gas pip-
ing and gas appliances in building ANsI/223. 1a/
enerco Group, Inc. | Gas-Fired Infra-Red space Heaters
NFPA54 Pamphlet, Table C-3 shows capacity of pipe of
different diameters and lengths in cubic feet per hour
for Natural Gas with pressure drop of 0.3 inches specify
gravity of 0.60. For liquefied Petroleum Gas (lP) capac-
ity refer to Table C-3 and C-15 of the same pamphlet.
For recommended heater gas connection refer to
Figure No. 5, Page 15. In Canada refer to CAN 1-B149.1,
and CsA B63.
If gas lines are to be pressure tested with compressed
air, disconnect each heater to prevent control damage
and cap outlets. After reconnecting all heaters, purge
gas lines of air and check all connections for leaks us-
ing soap solution.
warning:
Do NoT Use MATCH oR oTHeR
FlAMe FoR leAK TesTING.
5. piping reQuireMents
All piping installed must comply with local codes and ordinances
or with the National Fuel Gas Code, ANsI Z223.1 (NFPA 54),
whichever takes precedence. When installing piping, the following
requirements must be taken into consideration:
• Use new properly reamed black pipe free from chips.
• Apply a good quality pipe compound to all male threads
prior to assembly. If l.P. gas is the fuel, ensure that pipe
compound is resistant to l.P. gas. Do NoT Use TeFloN
™ tape.
• Prior to installation, apply pipe compound to all male
threads as shown in Figure 1.
use MOderate aMOunt OF pipe dOpe
leAVe FIRsT 2 THReADs BARe
Figure 1. Pipe Compound Application
• Male threads on pipe to be installed into gas valve shall
meet the requirements of Figure 2. Threads longer than
those shown in the figure may cause gas valve distortion
and malfunction.
• A sediment trap meeting the typical requirements of
Figure 3 shall be installed in the line to the gas valve.
• A dedicated shutoff valve for the heater must be in-
stalled in the gas supply line.
¾" MAXIMUM THReAD leNGTH
½" BlACK PIPe
GAs VAlVe BoDY
e3
operating Instructions and owner's Manual
Figure 2.
Gas valve
connection
requirements