Nemo D4-L+
1.6
Energy pulses
(where provided)
Quantity that can be coupled:
↵
selects active / reactive
confirms
Pulse weight:
1Pulse /0,1kWh(varh) – 1kWh(kvarh) - 10kWh(kvarh) - 100kWh(kvarh)
↵
selects pulse weight
confirms
Width of the pulse:
50 – 100 – 200 – 300ms
↵
selects width of the pulse
confirms
1.7
Display Contrast
Selectable values:
1...10
↵
selects the value
confirms
8
active or reactive energy
2.0 Password
2001
Keep simultaneously pressed the
Load
password 1000
and confirms
moves the cursor
↵
increases the loaded value
confirms
2.1
External CT ratio
Ct =
external primary/secondary CT ratio
External CT ratio (Ct):
1...9999
moves the cursor
↵
increases the loaded value
confirms
Rapporto TV esterni
Vt =
external primary/secondary VT ratio
External VT ratio (Vt):
1,0...400,0
moves the cursor
↵
increases the loaded value
confirms
Limit produced ratios
CT
x
For voltage direct connection
By modifying the
CT
and/or
reset.
2 keys
until you display page:
(ex.: CT 800/5A Ct = 160)
(ex.: TV 600/100V Vt = 6)
VT
(CtxVt): 100000 (CT/5A) - 400000(CT/1A)
load Vt=1,00
(with external voltage transformer)
VT
ratios, the KWH meters are automatically
03/16 10783521 WEB E cod.MF6HT...