1.5
RS485 Communication
(where provided)
According to the models, this meter can be without communication or equipped with
RS485 ModBus RTU / TCP or RS485 BACNET
1.5a
RS485 ModBus RTU / TCP Communication
Address number:
1...255
oves the cursor
↵
increases the loaded value
confirms
Transmission speed:
4,8 – 9,6 – 19,2 kbit/s
↵
selects speed
confirms
Parity bit:
none – even – odd
↵
selects parity
confirms
Waiting time before answer
moves the cursor
↵
increases the loaded value
confirms
It is usually advisable to load 003 (3ms). If, in the connection to other interfaces the
communication is lacking, try to increase the value.
03/16 10783521 WEB E cod.MF6HT...
communication.
:
3...100ms
(time-out)
1.5b
RS485 BACNET Communication
Address:
0...127
moves the cursor
↵
increases the loaded value
confirms
Transmission speed:
9,6 – 19,2 – 38,4 - 76,8 kbit/s
↵
selects speed
confirms
Parity bit:
none – even – odd
↵
selects parity
confirms
Network address:
0...4000
moves the cursor
↵
increases/decreases the loaded value
confirms
Nemo D4-L+