Error messages
Error
Fault
no.
Er07
LED:
Compressor:
Evaporator fan
(internal):
Condenser fan
(external):
Fault signal contact:
Er08
LED:
Compressor:
Evaporator fan
(internal):
Condenser fan
(external):
Fault signal contact:
Er15
LED:
Compressor:
Evaporator fan
(internal):
Condenser fan
(external):
Fault signal contact:
Operating Manual DTS and DTI 6201C / 6301C Standard Controller (SC) 086100015 © Pfannenberg GmbH
Unit activity
Possible causes
Blinking
Sensor 1 Maximum:
ON
The maximum value of the
switch cabinet temperature
ON
"Lit¯" (display) has been
reached or exceeded.
ON
The cooling unit cannot
Open
sufficiently cool the air in
the switch cabinet.
Blinking
Sensor 2 (TS2) defective.
ON
ON
ON
Open
Blinking
Anti-freeze (optional):
Anti-freeze sensor ≤ 1°C.
OFF
Safety shut-off, because
OFF
there is a risk of icing of the
compressor.
OFF
Open
Corrective measures
 Check the settings of the
cooling unit.
 Clean the heat
exchanger fins
(internal/external).
 Check evaporator fan
(internal) for function.
 Check the refrigeration
circuit for escaping
refrigerant or leaks.
 If necessary, install a
cooling unit with a higher
cooling capacity.
 Replace Sensor 2
according to the unit
type.
 Sensor 2 is plugged into
the circuit board, not
permanently soldered in
place.
 Restart after
accumulating
condensate water has
evaporated.
 A restart is only possible
with disconnection and
re-connection of the
mains voltage.
 For safety reasons, no
other means of resetting
is provided.
 Clean the heat
exchanger fins
(internal/external).
Inspect the switch
cabinet for leaks.
 Select higher switch
cabinet temperature
setpoint.
 Check evaporator fan
(internal) function
Page 29 / 38