Heat Pump lockout temperature (T
activating Heat Pump lock. If the outside temperature is below the lock temperature set,
the indoor unit (in ventilation mode) and Auxiliary Heat will be activated until the outside
temperature reaches a differential of +5ºC with regard to the set lock temperature and the
Delta Off (T
) defined in Auxiliary Heat is surpassed. When the indoor unit switches from
off
Ventilation mode to Heat Pump mode there will always be a 90-second delay.
Range: -20°C (-4°F) / 4°C (39°F) in steps of 2ºC (3.6ºF). Default: -6ºC (21ºF).
T
out
- 20 ºC
Heat Pump Locked
T
: Outside temperature
out
There are 3 outside Temperature scenarios:
T
< T
outside
Lock Heat Pump
T
< T
Lock Heat Pump
outside
T
< T
Lock Heat Pump
Lock Aux.Heat
Note: for units that do not have the "Outside Temperature" mode parameter, the outside
temperature provided by the Cloud will be taken as the default.
Note: the auxiliary heat and heat pump lock outside temperature difference will be at least
ΔT
= 6ºC, and priority will be given to heat pump lock temperature over auxiliary heat lock
min
temperature.
Digital input
Allows you to activate or deactivate this function and change:
•
Activation. Allows to set the input as:
a.
Activation by state: the state is persistent, if the input is activated the machine will be
forced off until it changes state.
b.
Activation by edge: the status is punctual, only the on/off is sent when the opening or
closing condition is met for the first time.
•
Settings. Allows you to set the input as normally open or normally closed.
Lock Heat Pump
T
Lock Heat pump
+ ΔT = 5 ºC
Demand
ON
< T
Lock Aux.Heat
OFF
ON
< T
Lock Aux.Heat
OFF
ON
< T
outside
OFF
). It is used to set an outside temperature for
4 ºC
0 ºC
Heat Pump Unlocked
Indoor unit
ON (FAN Max.)
ON (FAN Min.)
ON (Set Mode)
OFF
ON (Set Mode)
OFF
* Auxiliary Heat active only for Heat mode and Auto mode.
Auxiliary
Heat Pump
Heat
OFF
ON
OFF
OFF
ON
ON*
OFF
OFF
ON
OFF
OFF
OFF
EN
18 ºC
17