BTL7-A/C/E5 _ _ -M _ _ _ _ -SF-F _ _
Magnetostrictive Linear Position Sensor – Rod Style
8
Adjust
NOTICE
Interference in function
Adjustment while the system is running may result in
malfunctions.
► Stop the system before performing adjustment.
Initial situation:
– BTL with float within measuring range
Activate adjusting
► Press
b
for at least 4 s.
⇒ Indication for adjustment is displayed.
⇒ The current position value is displayed again once
the button is released.
Set start point
► Bring float to the new start point.
► Press
a
for at least 2 s.
⇒ The new start point is set with the last valid start
value.
Adjust start value
► Use
a
and
to change the start value. The gradient
b
of the curve changes
(see page 14).
► End calibration procedure: Briefly press
simultaneously (< 1 s).
b
⇒ Set position value is saved.
For setting the end point, adjusting the end value, and
ending adjustment,
for ending see page 17.
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
16
english
> 4 s b
a
> 2 s
a
a
b
b
a
and
< 1 s
a
Displayed values (example)
At 0...10 V
5.39 V
2.00 V
5.39 V
1.04 V
0.00 V
0.00 V
0.90 V
2.00 V
b
0.90 V
At 4...20 mA
9.15 mA
6.00 mA
9.15 mA
4.82 mA
4.00 mA
4.00 mA
7.20 mA
6.00 mA
7.20 mA