Temporary metal concrete cover
Pour concrete flush
to top of box
(Plastic temporary cover removed)
Tape all holes
and seams
FIGURE 1 - Pre-pour configuration without Plastic cover
Applications: Ceramic Tile (See Figures A, B, or C)
Laminate Flooring (See Figures A, B, or C)
Carpet Flooring with Flat Flange (See Figure E)
VCT with Flat Flange (1/8" Min. Thick. See Fig. B)
7
9
FIGURE
3
Page 2
Pour concrete flush
to top of plastic
temporary cover
Tape all holes
and seams
FIGURE 2 - Pre-pour configuration with Plastic cover(s)
Applications: VCT or Carpet with Flush Flange (See Fig. D)
Finished Concrete with Flush Flange (See Fig. F)
4
3
1
2
7
5
8
6
Table 1
Catalog No.
Wiring Channel Areas
Wiring Chamber Volumes
CFB4G25E, xxCRE (2) 0.39 in [250 mm ]
(4) 41.5 in [680 cm ]
CFB4G30E, xxCRE (2) 0.40 in [261 mm ]
(4) 51 in [835 cm ]
4 GANG RECESSED STEEL CONCRETE FLOOR BOX FOR RECTANGULAR
Grease plastic cover(s)
after taping
Catalog no.'s CFB4G25E, CFB4G25CRE, CFB4G30E, CFB4G30CRE
CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with national and local electrical codes, communication
standards, the following instructions, and any instruction included with individual devices.
NOTICE: Ensure data/communications circuits are separated from lighting/power circuits in accordance NEC and CE code
requirements.
Use with 24GTCVRxx, 24GCCVRxx, and 2GAFBCVRxx series rectangular covers. Use with 24GTFFCVRxx, and 24GCFFCVRxx series
furniture feed rectangular covers.
Use with CFBS1R8CVRxx series round covers when used with the CFB4GS1R8ADAPTE round cover adapter.
Use with CFBS1R8FFCVRxx series round furniture feed covers when used with the CFB4GS1R8ADAPTE round cover adapter.
CFBS1R8FF4GDIVKIT partition system required for multi-service installations.
Use with CFBHUB2, 2 in. metallic conduit hubs, CFBHUB125PVC, 1-1/4 in. non-metallic hubs, or CFBHUB200PVC, 2 in.
non-metallic hubs, when used with the CFB4G30E and CFB4G30CRE series boxes. May be used in place of knockout plates as
needed.
CAUTION: PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING. FINISHED FLOOR TYPES CERAMIC TILE, VCT (Vinyl
Composition Tile) FLOORING, CARPET FLOORING, LAMINATE FLOORING, AND FINISHED CONCRETE FLOORING AFFECT THE
INSTALLATION METHOD.
BEFORE CONCRETE POUR, SEE FIGURES 1, 2, 3, A, B, C, D, E, and F
See Figures 1 or 2 for configuration of concrete covers. For installation applications of FLUSH or FLAT flange styles, see Figs.
A, B, C, D, E and F.
1.
Remove and retain four #8-32 flat head screws [1] from top four corners of the box.
2.
Remove top mounting flange [2] with temporary concrete cover [3] and plastic Cover [4] from box.
3.
Install leveling screws [5] as shown in Figure 3. Level box as required. Be sure to set height of the top of box or temporary
plastic cover to be flush with the finished level of the concrete pour.
4.
Make conduit connections in accordance with application and applicable electric codes. 2" trade size conduit hubs,
(CFBHUB2) or PVC conduit hubs (CFBHUB125PVC, CFBHUB200PVC) may be used in place of knockout plates [6] (CFB4G30E,
xxCRE only) as needed.
5.
For same side feed-thru wiring, remove non-metallic low voltage dividers [7] as necessary.
6.
Re-install top mounting flange [2] with temporary cover [3] and plastic Cover [4] using screws [1] removed in step 1.
(NOTICE: plastic Cover [4] is optional for certain floor applications, see Figures A - E for desired floor application).
7.
Use tape or other to seal all seams and openings outside of box. See Figures 1 and 2.
8.
Pour concrete flush to the top mounting plate [2] or plastic cover [4] as needed.
CFB4G25E
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD-3005
3/23
COVERS - Installation Instructions
CFBHUB2
Conduit Hub
2 in. trade size
(sold separately)
CFBHUB125PVC
PVC Conduit Hub
2-1/2"
1-1/4 in. trade size
3"
(sold separately)