Télécharger Imprimer la page

Tripp-Lite SmartOnline SU5000RT4UHVTAA Manuel Du Propriétaire page 20

Publicité

Les langues disponibles

Les langues disponibles

Operation
(continued)
Start Settings
The UPS can start up through the battery without AC power. The DEFAULT is ENABLE. When the UPS switches to battery it can
AUTO RESTART to work in an On-Line Mode when AC power is restored. DEFAULT is ENABLE.
From the SETUP MENU screen, scroll DOWN
START screen. From this screen, pressing ON moves you to a ENABLE screen. Pressing ON will ENABLE, while scrolling DOWN
takes you to a DISABLE screen. From here, press ON to DISABLE this function.
From the BATTERY START screen, pressing DOWN
ENABLE screen; press ON to ENABLE. Pressing DOWN
Charger Settings
From the SETUP MENU screen, scroll DOWN
CHARGER CURRENT screen. Press ON again. From here, you can scroll DOWN
4.0 A. Press ON to save your desired value. The DEFAULT selection is 0.7A.
Use the following table as a guide for charger settings based on the number of battery packs you are using.
UPS Charge Current Setting for 5/6kVA Models
Internal Battery Pack + External Battery Packs
Charge Current Setting
UPS Charge Current Settings for the 12kVA Model
Use the same charger current settings as the 5/6kVA models for each power module of the SU12KRT4UHW. The number of
connected external battery packs must be equal on each power module of the SU12KRT4UHW.
to the START SETTING screen. From here, press the ON button for the BATTERY
i
will take you to an AUTO RESTART screen. Pressing ON takes you to an
i
i
START SETTING
ENT
DOWN
UP
To ENTER
until you reach the CHARGER SETTING screen. From here, press ON to get to the
i
CHARGER SETTING
ENT
DOWN
UP
To ENTER
1
0.7A
takes you to a DISABLE screen. Press ON to DISABLE this function.
BATTERY START
ENT
DOWN
UP
AUTO RESTART
ENT
DOWN
UP
or UP
i
CHARGER CURRENT
ENT
DOWN
UP
2
3-6
1.5A
3.0A
20
*ENABLE*
ENT
DOWN
UP
DISABLE
ENT
DOWN
UP
*ENABLE*
ENT
DOWN
UP
DISABLE
ENT
DOWN
UP
to select current values between 0.7 and
h
CURRENT = 0.7A
ENT
DOWN
UP
CURRENT = 1.5A
ENT
DOWN
UP
CURRENT = 3.0A
ENT
DOWN
UP
CURRENT = 4.0A*
ENT
DOWN
UP
7 or more
4.0A
i

Publicité

loading