Type ATM2-T3-MB | Telegrams
TELEGRAMS
Function 04 Read Input Register
Register
3x0001
Temperature
3x0002
Temperature
3x0002
Temperature
Function 02 Read Discrete Input
Register
0x0001
0x0002
Note: The addresses 1x0003...1x0008 are read with the value "0".
Function 05 Write Single Coil
Register
Parameter
0x0001
reserved
0x0002
System of units
Temperature
134r0067/002;1: Frozen :29-Jan-2024
Parameter
Without filtering
Filtering 1 s
Filtering 10 s
Parameter
Sensor error – breakage
Sensor error – short circuit
SI
→ Imperial
[°C]
[°F]
Data Type
Signed 16 Bit
– 500...+ 1500
– 580...+ 3020
– 999...+ 9999
Signed 16 Bit
– 500...+ 1500
– 580...+ 3020
– 999...+ 9999
Signed 16 Bit
– 500...+ 1500
– 580...+ 3020
– 999...+ 9999
Data Type
Bit 0
Bit 1
Data Type
Bit 1
15
Value
Range
– 50.0 ... +150.0 °C
– 58.0 ... +302.0 °F
Overflow
– 50.0 ... +150.0 °C
– 58.0 ... +302.0 °F
Overflow
– 50.0 ... +150.0 °C
– 58.0 ... +302.0 °F
Overflow
Value
Range
0 / 1
ON - OFF
0 / 1
ON - OFF
Value
Range
0 / 1
SI (Default) -
Imperial