G
Type ATM2-T3-MB
Calibratable outside temperature measurement transducer Type ATM 2 - T3 - MB, with Modbus connection, in an impact-resistant plastic housing with
quick-locking screws, measures temperature (–50...+150 °C). International system of units SI (default) can be changed to imperial (via Modbus).
The on-wall sensor is used to detect the temperature in gaseous media. It is used outside or in wet rooms, in cold storage buildings and green-
houses, in the industrial sector and in agriculture. Installation on outside walls is preferably performed on the north side or in a protected place.
In case of direct solar irradiation, we recommend using our sun and ball-impact protection hood WS 03 (accessories).
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the
bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals. Uses internal
diagnostics to detect sensor breakage or sensor short circuit as errors. The error messages can be retrieved via Modbus. The sensor is factory-
calibrated; an environmental precision adjustment by an expert is possible.
TECHNICAL DATA
Voltage supply:
Power consumption:
System of units:
Data points:
Sensor:
Measuring range:
Deviation, temperature:
Zero point offset:
Ambient temperature:
Medium:
Bus protocol:
Baud rate:
Signal filtering:
Housing:
Housing dimensions:
Cable connection:
Electrical connection:
Process connection:
Permissible air humidity:
Protection class:
Protection type:
Standards:
Internal diagnostics:
ATM2-T3-MB
Type
Type ATM 2 - T3 - MB
ACCESSORIES
WS-03
134r0067/002;1: Frozen :29-Jan-2024
24 V AC (± 20 %); 15...36 V DC
< 1.2 W ⁄ 24 V DC
SI (default) or Imperial (switchable via Modbus)
Temperature [°C] [°F]
Pt1000, DIN EN 60751, class B
–50...+150 °C
typically ± 0.2 K at +25 °C
± 10 °C
Measuring transducer –30...+70 °C
clean air and non-aggressive, non-combustible gases
Modbus (RTU mode), address range 0...247 selectable
9600, 19200, 38400 Baud
0.3 s / 1 s / 10 s
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016)
108 x 78.5 x 43.3 mm (Tyr 3)
cable gland, plastic
(2x M 20 x 1.5; with strain relief, exchangeable, inner diameter 8 - 13 mm)
0.2 - 1.5 mm², using push-in terminals
by screws
< 95 % RH, non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014 ⁄ 30 ⁄ EU
Error 1 at sensor breakage
Error 2 at sensor short circuit
Outside temperature ⁄ wet room temperature measuring transducers
Weather and sun protection hood,
200 x 180 x 150 mm, stainless steel V2A (1.4301)
12
Rev. Data - V40
Danfoss
Part Number
134B9410
134B9425