Télécharger Imprimer la page

Vimar By-me 02951 Guide Rapide page 3

Publicité

02951
FRONT VIEW AND CONNECTIONS.
Operation
Fan coil speed button
setup button
Setpoint increase button
Automatic
Current temperature
Heating
Select sensor
Fan coil
Ambient
Setpoint decrease
speed
humidity
button
USING THE THERMOSTAT.
Automatic
The thermostat performs the function of a timer-thermostat, making the climate profile
programmed via the control unit, touchscreens, etc.
Timed manual
Available only if automatic mode is active, it enables modifying the temperature
setpoint to a settable value and for a settable time. When the set time elapses the
system goes back into automatic mode with the setpoint value for the day and the
current time.
To activate this mode, when the thermostat is on Automatic, tap the
button.
Manual
The temperature is adjusted according to the set setpoint (
tons).
Reduction
The temperature is adjusted according to the set Reduction setpoint (
buttons).
Away Mode
The temperature is adjusted according to the set Away setpoint (
buttons).
• Protection Mode
The temperature is adjusted according to the "antifreeze" setpoint
or "too hot"
(if on cooling). This mode, associated with the system protection,
prevents damage to the system or structure.
Off Mode
In this mode, the thermostat does not perform any type of temperature control and all
the actuators are shut down.
DISPLAY ICONS AND BUTTONS.
Change operating mode:
• Auto
• Manual
• Reduction
• Away
• Protection
• Off
Change fan-coil mode, only if fan-
coil enabled:
• Automatic speed
• Speed 1
• Speed 2
• Speed 3
Increase
Decrease
Select sensor to view (only if external
sensor fitted):
• Internal sensor
• External sensor
Buttons locked
Heating in progress
49400595C0 02 1812
External temperature
BUS line
sensor terminals
or
and
but-
and
and
(if on heating)
Cooling in progress
Heating with boost function
Cooling with boost function
View external sensor temperature
(if fitted)
Screed temperature alarm
Window open indicator
Room temperature or set setpoint
Unit of measurement of temperature
(°C or °F)
Relative humidity (only if configured)
Fan-coil speed (only if fan coil ena-
bled). The bars indicate the current
speed.
Automatic fan-coil speed (only if fan
coil enabled).
The thermostat display is very sensitive and, to ensure proper operation, you
need to make sure that the power supply of the BUS line has an earthing ter-
minal
properly connected to the earth of the electrical system.
INSTALLATION RULES.
• The appliance must be installed in flush- or wall-mounting boxes with the relevant
mounting frames and cover plates, at a height of 1.5 m off the floor, in a suitable
position for correctly detecting the ambient temperature. It must not be installed in
niches, behind doors and curtains or in areas affected by sources of heat or atmos-
pheric factors. In particular, it must not be installed on outer walls or in association
with appliances that generate heat (e.g. regulators or lamps).
• Installation should be carried out by qualified personnel in compliance with the
current regulations regarding the installation of electrical equipment in the country
where the products are installed.
REGULATORY COMPLIANCE.
EMC directive. Standards EN 50428, EN 50491.
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the pro-
duct must not be included with other general waste at the end of its working life. The user
must take the worn product to a sorted waste center, or return it to the retailer when pur-
chasing a new one. Products for disposal can be consigned free of charge (without any new
purchase obligation) to retailers with a sales area of at least 400 m
than 25 cm. An efficient sorted waste collection for the environmentally friendly disposal of
the used device, or its subsequent recycling, helps avoid the potential negative effects on
the environment and people's health, and encourages the re-use and/or recycling of the
construction materials.
Thermostat pour système domotique avec écran tactile, pour le contrôle de
la température ambiante (chauffage et climatisation), gestion des installations
à 2 et 4 tubes, commande des ventilateurs à 3 vitesses et proportionnelle,
dispositif de contrôle de la température classe I (contribution 1%) en mode
ON/OFF, classe IV (contribution 2%) en mode PID, 1 entrée pour capteur NTC
de température filaire ou encastrable, rétroéclairage à led RGB, interfaçable
avec actionneur à sorties analogiques proportionnelles 01466 pour réaliser un
thermostat d'ambiance modulé de classe V (contribution 3%), à compléter
avec les plaques Eikon, Arké ou Plana - 2 modules.
Le thermostat s'intègre au système domotique By-me pour la gestion du réglage
thermique dans les installations à 2 ou 4 tubes (chauffage/climatisation) avec une
zone neutre (uniquement dans les installations à 4 tubes) et une fonction boost qui
active une seconde source afin d'obtenir plus vite le confort thermique souhaité.
Le thermostat est équipé d'un écran à rétroéclairage RVB et de 5 touches capaci-
tives pour la commande du point de consigne de la température, de la vitesse du
ventilateur et de la configuration des modes de fonctionnement du thermostat. Le
réglage de la couleur de l'écran s'effectue sur la centrale (21509) ou avec le logiciel
EasyTool Professional. Le thermostat est un dispositif universel à 2 modules pour
les séries Eikon, Arké et Plana.
CARACTÉRISTIQUES.
• Tension nominale d'alimentation : BUS 29 V
• Absorption typique : 5 mA
• Bornes : 2 bus TP, 2 pour capteur de température extérieure
• Différentiel thermique : réglable de 0,1° C à 1° C. Le réglage s'effectue sur la
centrale.
• Précision de la mesure de température
- Capteur intégré : ± 0,5° C entre 15° C et 30° C, ± 0,8° C aux extrêmes
- Capteur extérieur auxiliaire : idem capteur intégré Au-delà de la température de
fonctionnement du dispositif, l'erreur du capteur extérieur auxiliaire augmente
(max. 2,5° C à 80° C).
• Longueur maximale du câble de branchement du capteur extérieur : 60 m. Utiliser
un câble torsadé ayant une section supérieure à 0,5 mm
• Gestion des installations à 2 et 4 tubes
• Chauffage, climatisation, zone neutre (uniquement 4 tubes)
• Pilotage par actionneur By-me spécial des vannes chaud/froid On/Off avec action-
neur 01471 et proportionnelles (0-10 V, 4-20 mA) avec actionneur 01466
• Gestion ventilateur (3 vitesses/proportionnelles, vannes On/Off)
• Algorithme ON/OFF ou PID à sélectionner
- L'algorithme ON/OFF est un contrôle qui éteint le chauffage quand la tempéra-
ture prédéfinie, augmentée d'une valeur de seuil, est dépassée (et inversement
pour la climatisation) et le rallume quand la température ambiante redescend
sous la température prédéfinie.
- Le PID est un algorithme avancé qui stabilise la température dans la pièce en
allumant et éteignant l'installation avec le même résultat qu'une augmentation
ou une diminution graduelle de la puissance thermique (ou réfrigérante). Ce
système convient très bien aux installations au sol, l'algorithme doit être calibré
en fonction du type de pièce et de l'installation.
2
, if they measure less
(art. 01840).
2
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com

Publicité

loading