Télécharger Imprimer la page

IFM Electronic AS-interface AC5246 Notice D'utilisation page 11

Publicité

Les langues disponibles

Les langues disponibles

Installation
Notes on installation from page 26.
Addressing
At the factory the address is set to 0.
Addressing with the AC1144 addressing unit
When mounted and wired the module can be addressed with the
addressing cable (E70213) via the implemented addressing interface.
If a slave with the extended addressing mode is used in combination
with a master of the first generation (version 2.0), the parameter P3
must be 1 and the output bit D3 must be 0*. The output bit D3 and
the parameter bit P3 must not be used.
If a slave with the extended addressing mode is used in combination
with a master of the first generation (version 2.0), an address between
1A and 31A must be assigned to this slave.
Electrical connection
Connect the plugs of the sensors to the M12 sockets.
Cover the unused sockets with protective caps (E73004)*, the addres-
sing socket with the supplied protective cap. Tightening torque
0.6...0.8 Nm.
To guarantee protection rating IP 67 you also have to
• use the flat cable end seal (E70413)* if the module is at the end of
the cable line
• discharge exhaust air via the tube connection
If the AirBox is operated with silencer, the protection rating is
IP65.
*
* to be ordered separately
Default setting
11

Publicité

loading

Ce manuel est également adapté pour:

As-interface ac5249