7-3. Others
This section is described in the instruction manual supplied
with the timer remote contoller (CZ-RTC2).
Regarding the High-spec Wired Remote Controller
(CZ-RTC3), refer to the instruction manual supplied with the
model CZ-RTC3.
(1) Checking After Installation
1) Check that there are no gaps between the unit and
the ceiling panel, or between the ceiling panel and the
ceiling surface.
* Gaps may cause water leakage and condensation.
2) Check that the wiring is securely connected.
* If it is not securely connected, the auto flap will not
operate.
("P09" is displayed on the remote controller.)
In addition, the water leakage and condensation may
occur.
(2) Operating the Wireless Remote Controller
For details of installation, refer to the section "Wireless
Signal Receiver" in the supplied installation instructions.
(3) Selecting DC Fan Motor Tap (4-Way cassette)
Check the optional parts accordingly in the following
table.
Table for DC Fan Motor Tap Setting
Remote controller
Setting No.
setting data
Item code 5d
0003
(3)
0003
(6)
0006
*1 When using optional parts in different setting No. in
combination with multiple units, conform it to the larger
setting No.
1) When setting from the P.C. Board
<Procedure>
Stop the system before performing these steps.
1 Open the electrical component box cover, then
check the indoor unit control PCB.
2 Connect the jumper connector (2P: yellow)
which was supplied with the optional parts to the
correct connector pin on the indoor unit control
PCB according to the setting number which was
confirmed in Table for DC Fan Motor Tap Settings.
Setting No. (3) :
Then connect the jumper connector to the
connector pin TP3 (2P: yellow) on the indoor unit
control PCB.
Setting No. (6) :
Then connect the jumper connector to the
connector pin TP6 (2P: white) on the indoor unit
control PCB.
Contents &
optional parts name
Air-blocking material
(for 3-way air discharge)
Air-blocking material
(when a discharge duct is
connected)
Air-blocking material
(for 2-way air discharge)
21
2) When setting with the Wired Remote Controller
<Procedure>
Stop the system before performing these steps.
1 Press and hold the
,
simultaneously for 4 seconds or longer.
2 If group control is in effect, press the
and select the address (unit No.) of the indoor unit
to set. At this time, the fan at the indoor unit begins
operating.
3 Designate the item code
Temperature Setting
4 Press the timer time
desired setting data.
* For item codes and setting data, refer to "Table for
DC Fan Motor Tap Setting".
5 Press the
button.
(The display stops blinking and remains lit, and
setting is completed.)
* If air-blocking material is used, use the same
procedure as in steps 3 – 5 above and change
the setting for item code "62" to "0000."
If you wish to change the selected indoor unit,
follow the step 2.
6 Press the
button to return to normal remote
controller display.
6
1
5
Fig. 7-10
and
buttons
button
by adjusting the
/
buttons.
/
buttons to select the
2
3
4