Télécharger Imprimer la page

Mitsubishi Electric MLZ-KP09NA-U1 Notice D'installation page 6

Publicité

Les langues disponibles

Les langues disponibles

Unit suspension procedures
• Adjust the length of the bolt's protrusion from the ceiling surface before-
hand.
• Check the pitch of the suspension bolt
× 1051 mm))
1) Install special washer
and their nuts
in advance.
E
* Do this in the following order (from the top): nut
with cushion
, special washer
* Position special washer, with cushion
pointing down, as in the figure.
2) Lift the unit into place, aligned properly with suspension bolt
the bracket between special washer, with cushion
washer
, which are already in place, and secure it. Do the same in
all four places.
* Make sure the suspension bolt
from the surface of the ceiling. Otherwise you will not be able to install
the grille (optional).
* If the points for securing the grille are not flush with the ceiling
surface, water may condense, or the panel may not open/close.
3) If the long opening in the bracket and opening in the ceiling do not
align, adjust them until they do.
4) Check that the four places for securing the grille are all level using a
spirit level.
5) Tighten all the nuts.
Secure
1 Push
2-2. HOLE DRILLING
1) Determine the wall hole position.
2) Drill a dia. 2-15/16 in. (75 mm) hole. The outdoor side should be 3/16
to 1/4 in. (5 to 7 mm) lower than the indoor side.
3) Insert wall hole sleeve
K
.
2-3. DRAIN PIPING
• Use drain pipe
B
for drain piping. Be sure to connect the piping joints
using adhesive of polyvinyl chloride family to prevent leakage.
• Before drain piping work, remove the pipe cover, hose band, pipe band,
and spacer (cushion). Dispose of the spacer (cushion), as it will not be
needed.
• Drain hose
is 21-5/8 in. (550 mm) long, so that drain piping exit can be
moved up. Cut drain hose
into appropriate length before connecting.
En-5
E
. (12-1/8 × 41-3/8 in. (308 mm
F
onto the suspension bolt
F
, special washer
, nut
F
, nut
.
G
with the insulated surface
E
. Pass
and special
E
extends 2-3/4 in. (70 mm) or more
2 Secure
3 Position in the
center
1
2
Suspension bolt (W 3/8)
E
Nut with flange (W 3/8)
F
Special washer (with cushion, 4 pcs)
Nut with flange (W 3/8)
F
Nut (W 3/8)
G
Point for securing grille
Point for securing grille
Make sure these
surfaces are flush
with each other (0 to
1/8 in. (0-3 mm)).
Ceiling surface
Drain pan
Point for securing grille
Wall
ø2-15/16 in.
3/16 to 1/4 in.
(ø75 mm)
(5-7 mm)
Outdoor side
Hose band
Indoor unit side
16-15/16 in. (430 mm)
Cut within this area
Special washer
Enlarged view
Make sure these
surfaces are
flush with each
other (0 to 1/8 in.
Unit
(0-3 mm)).
Point for securing grille
Pipe band
Pipe cover
Spacer (cushion)
21-5/8 in. (550 mm)
Drain piping side
(Connect drain
pipe
)
B

Publicité

loading

Ce manuel est également adapté pour:

Mlz-kp09naMlz-kp12naMlz-kp18naMlz-kp12na-u1