Delta D4-h
Control
Manual Test
Verifies the proper working of earth leakage relay, included the output relays
Local
Front key
Test / Reset
Remote
External contact make, terminals 7-8
After having carried out the Test, display alternatively shows
Manual-Reset
Local
Front key
Test / Reset
Remote
External contact make, terminals 4 - 6
After having carried out the Reset, display alternatively shows
Test manuale no Trip
Verifies the proper working of earth leakage relay, without causing the output relay switching
Front key
(IΔn)
+
(IΔn)
simultaneously pressed
Displayed message
tnt +
contemporaneous switching on of
By releasing the keys, if the meter is properly working, message
When the test is over, the earth leakage relay automatically returns in monitoring condition
Test.
12
(not possible with d.c. extra supply voltage)
000 / tSt
rES / 000
4 LED's
(ma /
/ s / Prog)
YES
is displayed
Programmed parameter modification
If it is necessary to modify a parameter of the meter (once the device is programmed),
it is possible to enter the programming menu and directly access the parameter to modify,
without having to scroll the whole menu.
↵
Keep pressed the
Prog
key until the page
Press
Appears
000
Load
100
and confirm
Using the keys
scroll the parameters
Press the
Prog
key to enter and modify the programming
With the first pressure of the
Prog
key, it is displayed the value for that parameter actually
stored
Modify the parameter, then keep pressed the
Press once again
Prog
The message
nO
is displayed
↵
Act on to display
YES
Confirm by pressing
In any moment of the programming phase, it is possible to exit the menu without modifying
any parameter, by keeping pressed the
Press once again
Prog
↵
The message
nO
is displayed
Confirm by pressing
The message
bo
is displayed
The meter leaves the programming menu without modifying any parameter
Key
Message
Parameter
Mod
Function
Idn
Intervention threshold
dt
Intervention delay
rEL
State of reay
L.2
Alarm 2
rSt
Reset
FLt
Armonic filter
dd
RS485 address
b u
RS485 communication speed
P r
RS485 parity bit
tIN
RS485 waiting before answer
S V
Backup
P S
is displayed
Prog
key until appears the wording
Prog
key until appears the wording SAV
Value
ELR standard - MON monitor
30mA...30A
0...5s
Normally energized or de-energized
Alarm 2 contacts / alarm + pre-alarme / alarm + remote control
Manual or automatic
On / Off
1...255
4,8 - 9,6 - 19,2 - 38,4 Kbit/s
Even - odd - none
9...99ms
LE12570AA_E 10/20 - 01IM cod.RDD421..
S V
Point
2
3
4
5
6
7
8
9
10