Programmable parameters
Feed the meter, terminals 1 and 2
1
P S
ccess Password
↵
Keep pressed
Prog
key until the page
Press
000
is shown
Load password
100
and confirm
TTENTION
During the whole programming phase the
meter is not in monitoring phase but in programming phase.
increases the loaded value
reduces the loaded value
↵
moves the cursor
confirms
↵
2
Mod
Press
The meter can be used in
ELR
ELR
active protection
(standard working for earth leakage relay)
Mon
non-active protection; the meter just works as leakage current display
↵
function selection
confirms
↵
2.1
In the event the
Mon
function is selected
Press
nO
programming is not backed up and you leave the phase or
YES
programming is backed up
↵
function selection
confirms
The meter just works as display, alternatively showing Mon wording and the IΔn lea-
kage current instantaneous value
LE12570AA_E 10/20 - 01IM cod.RDD421..
P S
key until the page
LED Prog
is blinking, signaling that the
or
Mon
function.
S V
page appears
(monitor),
(together with the turning on of
or
m
metering unit LED)
2.2
If the
ELR
appears the
↵
function selection
confirms
3
Idn
↵
Intervention Point Selection
Press
Selectable values: 30mA...30A (19 ranges)
30mA
IΔn
↵
range selection
confirms
4
dt
↵
Intervention Delay Selection
Selectable values Δt(s): 0 – 0,06 – 0,15 – 0,25 – 0,5 – 1 – 2,5 – 5s
Press
↵
value selection
confirms
Set point (IΔn)
Selected delay Δt(s)
Non-operating time at @ 2IΔn
(setting backup)
Max. delay @ 5IΔn
TTENTION
by selecting the intervention threshold at 30mA
delay is automatically excluded
5
rEL
↵
State of Relay Selection
Press
Selectable values:
↵
state selection
confirm
active protection function is selected
(earth leakage relay standard working)
S V
page
(setting backup)
50mA
75mA
100mA
150mA
1A
1,5A
10A
15A
30mA
0s
0,06s
0,15s
0,25s
0,06s
0,15s
0,25s
0,03s
0,13s
0,22s
0,44s
(see previous point)
(it is not possible to select other values besides Os)
Terminals 17-18-19
nd
= negative security
(normally de-energized)
nE
= positive security
(normally energized)
Delta D4-h
,
200mA
300mA
500mA
750mA
2A
3A
5A
7,5A
20A
30A
50mA...30A
0,5s
1s
2,5s
5s
0,5s
1s
2,5s
5s
0,7s
1,8s
3s
5,5s
the intervention
or
9