Code
Level Descr.
dFd
1
Fans deactivated during defrosting
0 = fans activated (operation set from FPt)
1 = fans deactivated
FCO
1
Fans activated with compressor off
0 = fans deactivated
1 = fans activated (operation set from FPt)
2 = fans in duty cycle operation
UK
1
Fans ON time during duty cycle operation (FCO=2)
Fon
FoF
1
Fans OFF time during duty cycle operation (FCO=2)
List of
AFd
1
Temperature alarm threshold differential
This sets the re-entry temperature threshold after a high- or low-
temperature alarm condition
1
Maximum alarm threshold
HAL
Above this value (absolute or referred to the setpoint) an alarm is
triggered
If the reference is relative, the unmarked value is added to the setpoint
LAL
1
Minimum alarm threshold
Below this value (absolute or referred to the setpoint) an alarm is triggered
If the reference is relative, the unmarked value is subtracted from the
setpoint
PAO
1
Temperature alarm delay at power-on
dAO
1
Temperature alarm delay after defrost
The time, starting from the end of the dripping phase, during which no
alarm is signalled.
In the event of contemporaneous network defrosting, the time refers to the
defrosting end command
OAO
1
Temperature alarm delay after door closure
The time, after the door is closed again and during which no alarm is
signalled
1
Defrosting alarm timeout enabling
dAt
This enables the signalling of any defrosting end due to the maximum
time limit being reached (timeout).
0 = signal disabled
1 = signal enabled
List of
ndt
1
Decimal point display
0 = display without decimal point
1 = display with decimal point.
ddL
1
Display during the defrosting phase
0 = normal display (as set from the ddd par.)
1 = freezes the temperature value displayed at the start of defrosting until
the end of defrosting and the reaching of the setpoint
2 = "dF" until the end of defrosting and the reaching of the setpoint
The ddL parameter can be controlled only if the standard display
(ddd par.) includes the adjustment probe (probe 1 or network probe)
Ldd
1
Defrosting display block timeout
The time, starting from the end of defrosting (end of dripping phase),after
which the normal display is in any case restored
dro
1
°C or °F selection
0 = °C
1 = °F
This selection only affects temperature measurements. The values of the
parameters concerning temperature maintain their current values and
therefore, they must be varied manually to adapt them to the Fahrenheit
scale.
List of
1
Keyboard lock
LOC(*)
0 = keyboards disabled
1 = main terminal keyboard enabled
2 = secondary terminal keyboard enabled
3 = keyboards enabled (the first to request a service has precedence until
completion)
rEL
1
Software release
A read-only value that identifies the software version
List of
dEA
1
Supervision network address (for Master only)
The address to be set on each master must take into account the number of
slaves present in the LAN network preceding it: "dEA"="dEA[previous
master]"+"L01[previous master]"+1
The Supervision network address for a Slave is "dEA[master]"+"L00")
(*) Note : To release the keypad, hold down "SET" and "ON/OFF" together for at least 5 seconds.
alarm parameters
-ALr
-diS
display parameters
configuration parameters
-CnF
-LAn (**)
network parameters
Range
Unit
MBP
0,1
flag
0 ... 2
1 ... 60
min
15
1 ... 60
min
15
1.0 ... 90.0
°C [°F]
-50.0 ... 199.0
°C [°F]
10
-50.0 ... 199.0
°C [°F]
-10
0 ... 10
h
0 ... 999
min
60
0 ... 10
h
0,1
flag
0,1
flag
0,1,2
0 ... 255
min
0,1
flag
0 ... 3
0.0 ... 99.9
1 ... 199
BLOCKSYSTEM FS Pag. 28 Rev. 02 02/07
LBP
HBP
1
1
0
0
0
0
15
15
15
15
2
2
2
10
10
-10
-10
4
4
4
60
60
0
0
0
0
0
0
1
1
1
0
0
0
6
6
6
0
0
0
1
1
1
-
-
-
1
1
1