For the following items, take special care during
construction and check after installation is finished
Tick
when
checked
Is the indoor unit fixed firmly?
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
Are wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
Are the air filters fixed properly (when installing with rear duct)?
Maintenance of the air filters can be impossible.
Notes to the installer
Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.
Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.
I
MPORTANT INFORMATION REGARDING THE
REFRIGERANT USED
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.
Refrigerant type:
R410A
(1)
GWP
value:
1975
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.
FMDQ50~125A7V3B
Air conditioning system
4PW47630-1
S
ELECTING INSTALLATION SITE
(See figure 1 and figure 2)
1
Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.
-
Where optimum air distribution can be ensured.
-
Where nothing blocks air passage.
-
Where condensate water can be properly drained.
-
Where the false ceiling is not noticeably on an incline.
-
Where sufficient clearance for maintenance and service can
be ensured.
-
Where piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manual of
the outdoor unit.)
-
This is a class A product. In a domestic environment this
product may cause radio interference in which case the user
may be required to take adequate measures.
-
Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and noise in
those electrical appliances. (Noise may be generated
depending on the conditions under which the electric wave is
generated, even if 1 meter is kept.)
2
Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.
Service space ≥300
1
2
Drain pipe
3
Power supply wiring port
4
Transmission wiring port
5
Maintenance drain outlet
6
Gas pipe
7
Liquid pipe
P
REPARATIONS BEFORE INSTALLATION
1
Relation of ceiling opening to unit and suspension bolt position.
(See figure 3)
Model
FMDQ50
FMDQ60
FMDQ71~125
1
Indoor unit
2
Pipe
3
Suspension bolt pitch (x4)
4
Suspension bolt pitch distance
For installation, choose one of the possibilities as listed further.
Standard rear suction (See figure 6a)
1
Ceiling surface
2
Ceiling opening
3
Service access panel (optional accessory)
4
Air filter
5
Air inlet duct
6
Duct service opening
7
Interchangeable plate
A
B
700
750
1000
1050
1400
1450