Setup Wizard
The first time the RDB160BNU is powered on, a wizard is available to easily set up the device.
Name
P01
Application
P80
Temperature unit
P77
Fan output type
P78
Valve 1 output type
P79
Valve 2 output type *)
P58
BACnet MS/TP: MAC address
P59
BACnet MS/TP: Device
instance number, 4 digits on
right-hand side (e.g. 4567 in
1234567)
BACnet MS/TP: Device
P60
instance number, 3 digits on
left-hand side (e.g. 123 in
1234567)
P62
BACnet MS/TP: Baud rate
*) Locked to On/Off when thermostat is set to '2-pipe with electric heater' application.
Smart Infrastructure
3/4
Range
2 = 2-pipe system
3 = 4-pipe system
4 = 2-pipe system with electric heater
0 = Celsius
1 = Fahrenheit
0 = 1-, 2- or 3-speed fan
1 = DC fan
0 = DC valve
1 = PWM
2 = On/Off
3 = 3-position valve
0...127
Must be unique within the MS/TP network
0...9999
Please choose a device instance number
(P59 & P60) from 0...4194302
0...419
Please choose a device instance number
(P59 & P60) from 0...4194302
0 = 9600 bps
1 = 19200 bps
2 = 38400 bps
3 = 76800 bps
A5W00119632A-AA
Factory setting
3 = 4-pipe system
1 = Fahrenheit
0 = 1-, 2- or 3-speed fan
0 = DC valve
127
0
0
3 = 76800 bps
A6V12045441_en--_a
2022-04-14