MUST CONNECT
SWITCH TO CHARGE
EMERGENCY
BATTERY BACK
EMERGENCY TEST
SWITCH AND
INDICATOR LIGHT
NOTE: PLEASE FOLLOW THE STEPS ON PREVIOUS
PAGES FOR STANDARD INSTALLATIONS. ONCE
COMPLETED PLEASE FOLLOW THE STEPS BELOW
TO
ENSURE
PROPER
EMERGENCY BATTERY PACK.
page
5
EMERGENCY INSTALLATION (120V -277V ONLY)(PIXELATED)
LED DRIVER
EMERGENCY LED
DRIVER WITH
INTEGRATED BATTERY
INSTALLATION
OF
THE
1. EMERGENCY BATTERY PACK LUMINAIRES WILL HAVE ONE
EXTRA WIRE EXITING THE FIXTURE (RED). MAKE SUPPLY
WIRE CONNECTIONS ACCORDING TO THE APPROPRIATE
WIRING DIAGRAM BELOW. LUMINAIRES THAT WILL BE
SWITCHED ON/OFF MUST HAVE THE RED LEAD
CONNECTED TO AN UNSWITCHED INPUT LINE LEAD SO
SWITCHING THE LUMINAIRE OFF IS NOT SEEN AS A POWER
FAILURE. CONNECTING THE RED LEAD OF THE LUMINAIRE
TO THE SWITCHED INPUT LINE LEAD WILL RESULT IN
UNDESIREABLE PERFORMANCE AND MAY VOID LUMINAIRE
WARRANTY.
2. LOOSEN THE FOUR RETAINED 10-24 SCREWS ATTACHING
THE TOP COVER AND LIFT THE TOP COVER UP.
3. COMPLETE THE CONNECTION AS SHOWN BETWEEN THE
TWO RED WIRES. THIS MUST BE CONNECTED SO THAT THE
EMERGENCY BATTERY PACK STAYS CHARGED.
4. ONCE CONNECTED TUCK WIRES INSIDE GASKETED
SECTION. ALIGN TOP COVER CAST-IN ARROW TO CAST-IN
ARROW ON INSIDE OF LOWER HOUSING. CAREFULLY
PLACE TOP COVER BACK ON LUMINAIRE MAKING SURE
NOT TO PINCH WIRES BETWEEN THE TOP COVER AND
LOWER HOUSING.
5. REATTACH THE TOP COVER TO THE LUMINAIRE BY
TIGHTENING THE FOUR 10-24 SCREWS THAT WERE
LOOSENED IN STEP 2 TO 23 IN-LBS.
6. ONCE LUMINAIRE IS POWERED ON ENSURE THAT TEST
INDICATOR LIGHT TURNS ON. FOR A SHORT TERM TEST (30
SEC), LET THE UNIT CHARGE FOR AT LEAST AN HOUR
BEFORE PRESSING EMERGENCY BUTTON TO ENSURE
LUMINAIRE CAN SWITCH OVER TO EMERGENCY BATTERY
POWER.
EMERGENCY BATTERY PACK WIRING
UNSWITCHED LINE - - - - - - - -
UNSWITCHED LINE (RED)
SWITCHED LINE
443560819320-Rev E
UNSWITCHED LINE - - - - - - - -
UNSWITCHED LINE (RED)
SWITCHED LINE