Installation distances
C856T / C856TG Style
Combustible roof
465
INSTALLATION AGAINST COMBUSTIBLE WALLS
Combustible wall
200
Permitted area for
combustible parts
of the building
* If the stove is placed on a hearth plate made of glass for example (accessory), the height from the floor is affected by a distance corresponding to the thickness of the hearth plate, for a free standing
glass hearth plate this is 10 mm.
** To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
WHEN INSTALLING TURNTABLE (OPTION) the follow-
ing installation distances do not apply.
See the separate turntable installation instructions.
!
A separate glass hearth
plate (accessory)
increases the connection
height to the chimney by
10 mm.
400
Combustible wall
500
732
365
Ø150
183
46
Air inlet Ø67
113
INSTALLATION AGAINST FIREWALLS
Fire-retardant wall of
brick or concrete
50
700
Fire-retardant wall of
brick or concrete
200**
432**
The minimum distance in front of
the stove opening to combustible
parts of the building or interior
decoration must be at least 1,1 m.
The dimension diagrams only
show the minimum permitted
installation distances for the
stove. When connecting to a steel
flue, also note the safety distance
requirements of the flue. The
safety distance between an un-
insulated flue and a combustible
part of the building should be at
least 450 mm.
A = height from floor to chimney
connection upwards
B = height from floor to c/c chimney
connection rear
C = height from floor to air inlet
D = height from floor to lower edge
of hatch
750