4.11
Status values
The system's settings can be checked and adjusted via the remote control by following
these steps
Step 1: Press on
Step 2: Press on
Step 3: Press on
Parameters table
Parameters
D0
Ambient temperature
D1
Inlet water temperature
D2
Outlet water temperature
D3
Coil temperature
D4
Compressor
D5
Ventilator
D6
4-way valve
D7
High pressure protection
D8
Low pressure protection
D9
Flow sensor
4.12
Forced defrosting
When the heat pump is operating in heating mode:
1. Switch off the heat pump,
2. Press the button
3. Change parameter C34: by default, it is set to 0. Set it to 1 to activate it.
a. Select the desired parameter using the up and down arrows.
b. Press
to select the parameter to be adjusted.
c. Use the arrows to change the value of the parameter.
d. Press
to confirm, then exit the page.
4. Switch on the heat pump. The heat pump starts defrosting and the icon
When defrosting is complete, the heat pump restarts in heating mode.
25 |
EN
4. Use
until you enter the settings verification mode.
and
to see the parameters.
to select the setting to be viewed.
Indication
for 3 seconds to access the parameter modification page.
Adjustment range
-20°C- 80°C
Measured value
-20°C- 80°C
Measured value
-20°C- 140°C
Measured value
-20°C- 80°C
Measured value
ON/OFF
Measured value
ON/OFF
Measured value
ON/OFF
Measured value
--
ON/OFF
Measured value
--
flashes.
Comments