Technical Data
Type
Power supply
Nominal force
Nominal current
Nominal stroke length*
Running speed: ventilation (SHEV high-speed function)*
O1, O2
O3
C3
C2, C1
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Ambient humidity
Emission sound pressure level
Additional functions*
Opening and Closing Ranges
O1*
23 mm
2x 250 N
C1*
C2*
23 mm
77 mm
2x 150 N
2x 150 N
* Programmable with software SCS ** + approx. 20 % switch-off reserve (temporary)
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing ranges C3 and C2, the drive
runs "OPEN" for 10 seconds, then "CLOSE" again. If
closing is not possible after three attempts, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range C2
and C1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
99.827.08 1.2/10/18
CDC-TW-0502-0500-1-ACB
1,6 A
500 mm ± 2 %
6,7 mm/s (13,6 mm/s)
6,7 mm/s (6,7 mm/s)
6,7 mm/s (13,6 mm/s)
5 mm/s (5 mm/s)
>20.000 double strokes
30 % S6 (EN 60034-1)
Aluminium powdercoated (~ RAL 9006)
≤ 90 %, not condensing
Closing edge protection = activated (3 repetitions of stroke);
Locking relief = activated (retraction lift max. 0,2 mm)
O2*
2x 250 N
250 mm
2x 250 N
English
CDC-TW-0502-0800-1-ACB
24 V DC / ± 15 %
2x 250 N**
800mm ± 2 %
6,7 mm/s (15,0 mm/s)
6,7 mm/s (6,7 mm/s)
6,7 mm/s (15,0 mm/s)
5 mm/s (5 mm/s)
2x approx. 1500 N
IP 32
-5 ... +75 °C
30 min / 300 °C
LpA ≤ 35 dB(A)
C3*
CDC-TW-0502-1-ACB
2,0 A
O3*
15 mm
2x 250 N
7/20

Publicité