Télécharger Imprimer la page

Victron energy Quattro 12/5000/220-100/100-230V Manuel page 25

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 51
8. TECHNICAL SPECIFICATION
Quattro
PowerControl / PowerAssist
Integrated Transfer switch
AC inputs (2x)
Maximum feed through current (A)
Input voltage range (V DC)
Output
(1)
Cont. output power at 25°C (VA)
(3)
Cont. output power at 25°C (W)
Cont. output power at 40°C (W)
Cont. output power at 65°C (W)
Peak power (W)
Maximum efficiency (%)
Zero load power (W)
Zero load power in AES mode (W)
Zero load power in Search mode (W)
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
(4)
Charge current starter battery (A)
Battery temperature sensor
Auxiliary output (A)
(5)
Programmable relay
(6)
Protection
(2)
VE.Bus communication port
General purpose com. port
Remote on-off
Common Characteristics
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
Safety
Emission, Immunity
Vehicles, aftermarket
Anti-islanding
1) Can be adjusted to 60 HZ; 120 V 60 Hz
on request
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high
12/5000/220-100/100
24/5000/120-100/100
24/8000/200-100/100
48/5000/70-100/100
48/8000/110-100/100
Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz Power factor: 1
2x100
2x100
INVERTER
9,5 – 17V
Output voltage: 230 VAC ± 2%
5000
8000
4000
6500
3700
5500
3000
3600
10000
16000
94 / 94 / 95
94 / 96
30 / 30 / 35
45 / 50
20 / 25 / 30
30 / 30
10 / 10 / 15
10 / 20
CHARGER
14,4 / 28,8 / 57,6
28,8 / 57,6
13,8 / 27,6 / 55,2
27,6 / 55,2
13,2 / 26,4 / 52,8
26,4 / 52,8
220 / 120 / 70
200 / 110
4 (12V and 24V models only)
GENERAL
50
50
3x
3x
For parallel and three phase operation, remote monitoring and system integration
2x
2x
Operating temp.: -40 to +65˚C Humidity (non-condensing): max. 95%
ENCLOSURE
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
Four M8 bolts (2 plus and 2 minus connections)
Bolts M6
Bolts M6
34 / 30 / 30
45 / 41
470 x 350 x 280
444 x 328 x 240
470 x 350 x 280
444 x 328 x 240
STANDARDS
EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1
EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, EN-IEC 61000-6-3, EN-IEC 61000-6-2, EN-
12V and 24V models: EN 50498
3) Non-linear load, crest factor 3:1
4) At 25˚C ambient
5) Switches off when no external AC source available
6) Programmable relay that can a.o. be set for general alarm,
DC under voltage or genset start/stop function
AC rating: 230 V / 4 A
DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
23
48/10000/140-
100/100
Yes
Yes
2x100
19 – 33V
38 – 66V
Frequency: 50 Hz ± 0,1%
10000
8000
6500
4500
20000
96
55
35
20
57,6
55,2
52,8
140
Yes
50
3x
a-g
2x
Yes
Bolts M6
45
470 x 350 x 280
IEC 61000-6-1
See our website
48/15000/200-
100/100
2x100
15000
12000
10000
7000
25000
96
80
50
30
57,6
55,2
52,8
200
50
3x
2x
Bolts M6
72
572 x 488 x 344

Publicité

loading