Do Not Overload Generator
Overloading a generator in excess of its rated wattage
capacity can result in damage to the generator and to
connected electrical devices.
To prolong the life of your generator and attached
devices, follow these steps to add electrical load:
1. Start the generator with no electrical load attached.
2. Allow the engine to run for several minutes to
stabilize.
3. Plug in and turn on the first item. It is best to
attach the item with the largest load first.
4. Allow the engine to stabilize.
5. Plug in and turn on the next item.
6. Allow the engine to stabilize.
7. Repeat steps 5-6 for each additional item.
Parallel Operation (2 x SUA2000i Models)
WARNING
Fire and electrocution hazard. Never connect or
disconnect the parallel cord leads when a generator
is running. Do not parallel more than two generators.
Use only AIPOWER generators for paralleling.
NOTICE
Paralleling this generator to a generator that is not
compatible can cause a low voltage output that can
damage tools and appliances powered by the
generator. Do not connect or disconnect parallel
cables while the generator is running to avoid damage.
Parallel operation gives you the ability to link this
generator to a compatible AIPOWER generator for
combined running and starting power output. Use
only the AIPOWER approved cables for parallel
operation. For single generator operation, the parallel
operation cable must be removed.
NOTE:
Only connect two identical (same model) generators
together for parallel operation.
Set up and Operation
1. Align the two inverters on a firm, flat and level
surface at a minimum 20 inch apart.
WARNING
2. Both generators to be turned off and all electrical
loads disconnected before paralleling operation.
3. Make sure the LOW IDLE switch is in the OFF
position on both generators.
Page 16
If not spaced apart, the exhaust heat
from one generator discolors or melt
the plastic shell on other generator.
20"