EMERGENCY INSET 60 | 100
Mounting instruction
3/7
4 POLE SUPPLY LINE
N
N
LUMINAIRE CAN BE SWITCHED ON AND OFF WITH L`
L1
L`
BY DISCONNECTING THE VOLTAGE POWER SUPPLY FROM L, IT WORKS IN EMERGENCY MODE.
PE
PE
THE LUMINAIRE TESTS ITSELF ACCORDING TO IEC 62034. THE TEST DURATION IS 3 HOURS.
L1
L
3 POLE SUPPLY LINE / VARIANT 1
N
L´ IS NOT CONNECTED. THE LUMINAIRE JUST LIGHTS UP WHEN L HAS NO VOLTAGE APPLIED.
N
L`
THE EMERGENCY-LIGHT-FUNCTION TESTS ITSELF INDEPENDENTLY.
PE
PE
THE TESTING DURATION ACCORDING TO IEC 62034 LASTS 3 HOURS.
L1
L
3 POLE SUPPLY LINE / VARIANT 2
N
N
L` AND L ARE PROVIDED WITH A BRIDGE.
L`
THE LUMINAIRE IS CONSTANTLY IN NL-MODE
PE
PE
THE LUMINAIRE TESTS ITSELF ACCORDING TO IEC 62034.
L1
L
STATUS DISPLAY
THE SYSTEM STATUS GETS DISPLAYED ON A TWO COLOR LED.
LED DISPLAY
PERMANENT GREEN
FAST FLASHING GREEN
(0,1SEC ON - 0,1 SEC OFF)
SLOW FLASHING GREEN
(1SEC ON - 1 SEC OFF )
RED LED ON
SLOW FLASHING RED
(0,1 SEC EIN - 0,1 SEC AUS)
FAST FLASHING RED
(0,1SEC EIN - 0,1 SEC AUS)
DUBBLE FLASHING GREEN
GREEN AND RED OFF
COMMISSIONING
AFTER THE INSTALLING THE LUMINAIRE AND CONNECTING THE POWER SUPPLY AND THE BATTERY TO THE EM CONVERTER FOR THE FIRST TIME, THE UNIT WILL START CHARGING THE
BATTERY FOR 20 HOURS (INITIAL CHARGE). THE 20-HOUR RECHARGE HAPPENS ALSO WHEN THE BATTERY GETS CHARGED OR THE DEVICE LEAVES THE REST MODE. THE FOLLOWING
AUTOMATIC START UP TEST WILL ONLY BE DONE IF THE BATTERY GETS REPLACED OR IS FULLY CHARGED (AFTER 20 HOURS).
TESTS
COMMISSIONING TEST
A FULLY COMMISSIONING TEST IS CARRIED OUT AUTOMATICALLY AFTER A PERMANENT CONNECTION TO THE POWER SUPPLY AFTER 5 DAYS. THE FUNCTION OF A SIMPLE COMMISSIONING
SETS THE DATE AND TIME FOR THE INITIAL INSPECTION TO ENSURE RANDOM TESTING OF THE UNIT. FUNCTIONAL TESTS ARE CARRIED OUT WEEKLY 5 SECONDS LONG AND ARE
CONTROLLED FROM A MICROPROCESSOR. TO CHECK THE BATTERY PERFORMANCE, A FULL DURATION TEST IS PERFORMED ANNUALLY. YOU WILL FIND A COMPREHENSIVE DESCRIPTION OF
THE FUNCTIONS REGARDING COMMISSIONING AND TESTS IN THE APPLICATION NOTES.
XAL GmbH
Auer-Welsbach-Gasse 36
STATUS
COMMENT
SYSTEM OK
AC OPERATION
FUNCTIONAL TEST OPERATES
DURATION TEST OPERATES
LAST ERROR
OPEN CIRCUIT / SHORT CIRCUIT/ LED DEFECT
BATTERY FAULT
BATTERY HAS NOT RUN OR FUNCTION TEST FAILED. BATTERY IS DEFECTIVE
LOADING ERROR
WRONG CHARGING POWER
BLOCK MODUS
SWITCHABLE IN THE BLOK-MODUS WITH CONTROLLER BATTERY MODE
DC OPERATION
(STANDARD OPERATION)
A-8055 Graz
T:+43.316.3170.0
F:+43.316.3170.9000
www.xal.com
468007000054