Set-Up - ProMinent DULCOMETER DMT Mode D'emploi

Masquer les pouces Voir aussi pour DULCOMETER DMT:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Set-up

Parameter Profibus
Mode:
Bus-ON
Address: = 125
Limit value measured
variable
min. = 2.00 pH
max. =12.00 pH
16
®
The PROFIBUS
DMT is based on the complete function range of
the standard DMT but with added PPROFIBUS
The user can enable PROFIBUS
"Bus ON" operating mode from the operating menu.
In the "Bus ON" operating mode the DMT sends the relevant
information to a master (PLC, PC) via its gateway and the
®
PPROFIBUS
.
Set-up
®
The PPROFIBUS
-DMT settings are carried out in the "Bus OFF"
operating mode (see below) as with the standard DMT. Only the bus
functions are added. The user can alter only the operating mode in
the "Bus ON" operating mode (see below).
NOTICE
If you pause for longer than 60 sec. when carrying out a
setting, the settings procedure is cancelled.
Setting the PROFIBUS
Mode:
Bus-ON
Address: = 125
Having set the PROFIBUS
disconnected briefly for the PROFIBUS
Setting limit values for measured variable
min. = 2.00 pH
max. = 12.00 pH
When the user has set measured variable limits, DMT values which
exceed limit values trigger an error signal to the PROFIBUS
set limit values are also the measured variable values at which the
4 mA and/or 20 mA output current is accepted (see "Parameter
output" input menu).
®
functionality by selecting the
®
address
®
address, the supply voltage has to be
®
address to be accepted.
®
DP-functionality.
®
. The
ProMinent
®

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Profibus dp

Table des Matières