Télécharger Imprimer la page

Keysight RP7900 Serie Guide D'utilisation Et D'entretien page 52

Publicité

Les langues disponibles

Les langues disponibles

1 Quick Reference
NPLC @60Hz
Number of averaged points
1
3255
0.6
1953
0.1
325
0.06
195
0.031
100
0.010
33
0.006
20
0.003
10
0.0003
1
Excessive Dynamic Protection
For the high current models, EDP does not limit the allowable programmable waveform amplitude or
frequency. You can program a full scale square wave at a maximum frequency of 97.6 kHz indefinitely.
Output Quadrants
Model
+ V1
RP7931A /RP7941A
20 V
RP7933A /RP7943A
20 V
RP7932A /RP7942A
80 V
RP7935A /RP7945A
80 V
RP7936A /RP7946A
160 V
52
Voltage Measurement
Current Measurement
% of range added to spec.
% of range added to spec.
0
0.00013%
0.0005%
0.0009%
0.0015%
0.0025%
0.004%
0.006%
0.02%
+ V2
+ V3
+/- I1
12.5 V
0.5 V
400 A
12.5 V
0.5 V
800 A
40 V
1 V
125 A
40 V
1 V
250 A
80 V
1.5 V
125 A
0
0.0005%
0.004%
0.005%
0.008%
0.0015%
0.020%
0.03%
0.10%
+/- I2
Minimum sink
resistance
250 A
1.25 mΩ
500 A
625 µΩ
62.5 A
8 mΩ
125 A
4 mΩ
62.5 A
12 mΩ