This template must be used in conjunction with templates 7.2.1 or 7.2.2, depending on
termination shape (i.e. round, or round and square). See appropriate templates folder.
venting requirements
EN
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not
be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20
feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0" (0mm) rise per foot/meter however for optimum performance it is recommended that all
horizontal runs have a minimum 1/4" (21mm) rise per foot/meter using fl exible venting. For safe and proper operation of the
appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwell-
ings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" (31.8mm) air
gap all around between the inner liner and outer liner is required for safe operation.
This appliance is certified for use with a power vent kit. Contact your local authorized dealer for more information.
If approved for use with a power vent kit, state: "This appliance is certifi ed for use with a power vent kit. Con-
All vent measurements start at the base of the air collar of the appliance.
tact your local authorized dealer for more information."
If not, cover with a white box.
2.1
typical venting installation
WARNING
!
The first 2 feet of outer 8" (203mm)
diameter vent pipe from the ap-
pliance must be wrapped in the
1" (25mm) thick insulation sleeve
(supplied).
A
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when
final grading is completed, the bottom air slot is located a minimum 12" (30.5cm) above grade. The maximum
Special vent installation (periscope termination)
allowable vent length is 10' (3m) for a fireplace and 8' (2m) for a stove.
WARNING
!
The first 2 feet of outer 8" (203mm)
diameter vent pipe from the ap-
pliance must be wrapped in the
1" (25mm) thick insulation sleeve
(supplied).
14
W415-3150 / B / 03.15.23
AX36-1
AX42-1
54 7/8" (139.4cm)
57 7/8" (147cm)
insulated
sleeve
DRAFT
base of air collar
insulated
sleeve
30" (76.2cm)
minimum
base of air collar
20" (51cm)
maximum
20"
(51cm)
12"
(30.5cm)
minimum
to grade
A