D-EOMCP00104-14_02FR
Organigramme de démarrage et d'arrêt de la récupération de chaleur
5.26.2
Control requires loading
No
Loading interstage timer
32/37
expired
(PID calculation)
Yes
New circuit activation
Heat recovery activation
Heat recovery pump
start
No
Recovery flow switch
consensus within timer
expiration
Yes
HR temperature control
start
HR temperature control
stabilitation
HR circuits activation
enabled
No
HR leaving temperature
above limit
Yes
HR 3Way valve
complete opening
Control requires standby
System standby
Manuel d'utilisation
HR Trip
HR 3Way valve
modulating
Control requires
unloading
Unoading interstage
timer expired
(PID calculation)
Yes
Last circuit deactivation
EWYD_BZ
No