Télécharger Imprimer la page

Lenze ELN3-0150H024-001 Instructions De Montage page 3

Publicité

Les langues disponibles
  • FR

Les langues disponibles

GB
,
Please read these instructions and the documentation of the standard device
before you start working!
Observe the safety instructions given therein!
{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
Death or severe injuries when touching the power terminals.
ƒ
Protective measures:
Switch off the power supply and wait for at least three minutes before
ƒ
working on the power terminals.
Make sure that all power terminals are deenergised.
ƒ
Technical data
Enclosure
Insulation resistance
Temperature
Storage
Transport
Operation
Pollution
Vibration resistance
Mounting location,
mounting position
Rated data,
conformity/approval
EDKLN3TRK−001 DE/EN/FR/ES/IT 1.1
EN 60529
NEMA 250
EN 61800−5−1
EN 61800−5−1
EN 50178; IEC
61800−5−1;
Germanischer
Lloyd, general
conditions
Vertical in the control cabinet with fixing bracket below (with low masses,
it can also be suspended) ^ 10
See nameplate
IP 00
Protection against accidental
contact according to type 1
Overvoltage category III
> 2000 m: Overvoltage category II
−25 ... +60 °C
−25 ... +70 °C
−10 ... +55 °C
Current derating from +45 ... +55 °C: 2.5 %/°C
Pollution degree 2
Acceleration−resistant up to 1 g
3
l

Publicité

loading