• Attachment methods of connection cord
1) Remove the factory-mounted connector from S21.
2) Tie the harnesses in a bundle as shown in the figure so that the removed
connector does not interfere with the printed circuit board.
3) Attach the connection cord to the S21 connector and pull
the harness out through the notched part in the figure.
4) Pull the harness around, as shown in the figure.
• Attachment methods of metal plate electrical wiring
covers
1) Hook the top part of the metal plate electrical wiring
cover (B) on the 2 tabs.
2) Press in the hook on the bottom to catch a single tab, and
mount the metal plate electrical wiring cover (B).
3) Insert the connector into the hole, and hook and mount
the metal plate electrical wiring cover (A) onto the 4 tabs.
Refrigerant Piping Work
With a multi indoor unit
1.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward
so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
■English
, install as described in the installation manual supplied with the multi outdoor unit.
HA connector (S21)
Screw
Metal plate electrical
wiring cover (B)
(Cut exactly at
right angles.)
Flaring
Set exactly at the position shown below.
Flare tool for
A
R410A
Clutch-type
Die
A
0-0.5mm
Flare's inner surface
must be flaw-free.
Metal plate
electrical
wiring cover (A)
Remove burrs.
Conventional flare tool
Clutch-type
Wing-nut type
(Rigid-type)
(Imperial-type)
1.0-1.5mm
1.5-2.0mm
Check
The pipe end must
be evenly flared in a
perfect circle.
Make sure that the
flare nut is fitted.