ENG
3.4.6
Energy-saving mode
Fig. 7: Temperature sensor - TS2 for energy-saving mode
Cooling units with Multi-Controllers (MC) have an energy-saving mode.
There is a second temperature sensor TS2 (1) for this on the back of the cooling units which measures the switch cabinet
interior temperature.
Functional description:
In the delivery condition, the energy-saving mode is activated is no cooling request is received from the controller
for 15 minutes. The control panel then shows "En", see chapter "Controller", Page 16.
If the switch cabinet interior temperature measured by temperature sensor TS2 exceeds the set temperature
setpoint, the evaporator fan (inside the switch cabinet air circuit) is switched off.
The evaporator fan remains switched on until the switch cabinet interior temperature measured by the
temperature sensor TS2 exceeds the set temperature setpoint+2K hysteresis. The evaporator is then switched
back on and the energy-saving mode is ended.
Operating Manual | Attachment and Installation Cooling Units | Multi Controller (MC) – 400 / 460 V, 3~ | 086100124
G00068
21/76